Maintenance & Troubleshooting; Troubleshooting Tips - Honeywell HP1205UL-4 Product Installation Document

Power supplies/distribution units

Advertisement

5. Maintenance/Troubleshooting
Product should be tested annually for proper functionality. Normal verification of proper operation
includes measuring all outputs with a voltmeter under normal load conditions to ensure output voltage
is present.
Trouble shooting tips:
Symptom
All output LEDs are extinguished
Single output LED is extinguished
Battery not charging.
WARNING: TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, DO NOT
EXPOSE THIS APPLIANCE TO RAIN OR MOISTURE. RISK OF ELECTRICAL
SHOCK AND/OR EQUIPMENT DAMAGE. DISCONNECT POWER BEORE
SERVICING THIS APPLIANCE.
• MAINTAIN A 1/4" OF SEPARATION BETWEEN THE AC MAINS AND ALL LOW VOLTAGE WIRING.
• A READILY ACCESSIBLE SWITCHED CIRCUIT BREAKER MUST BE AVAILABLE TO DISCONNECT
MAIN POWER AS REQUIRED.
• THIS UNIT CONTAINS NO USER-SERVICEABLE PARTS, INSTALLATION AND SERVICING
SHOULD ONLY BE MADE BY QUALIFIED PERSONEL.
• INSTALL IN ACCORDANCE WITH LOCAL REGULATIONS AND NATIONAL ELECTRIC CODE.
CAUTION: RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE.
DISPOSE OF USED BATTERIES ACCORDING TO THE INSTRUCTIONS.
For additional information:
• Visit our website at http://www.honeywellpower.com
• Contact Technical Support at (877) HPP-POWR
• E-mail us at HPP.techserv@Honeywell.com
Check for
Measure for proper input voltage
(120VAC/240VAC) using an AC voltmeter.
Verify total output load. Check for
overload/Short circuit condition on all outputs.
Remove short or overload condition.
Verify output load on circuit. Check for
overload/Short circuit condition. Remove short
or overload condition.
Measure battery charger voltage to ensure
13.8VDC is present.
Check battery to make sure it is not worn out or
defective.