Lennox 12HPB Series Installation Instructions Manual page 15

Heat pump units
Hide thumbs Also See for 12HPB Series:
Table of Contents

Advertisement

Charging Using Normal Operating Pressures
and the Approach Method
Outdoor Temp. > 65_F (18_C)
The following procedure is intended as a general guide and
is for use on expansion valve systems only. For best results,
indoor temperature should be 70°F (21°C) to 80°F (26°C).
Monitor system pressures while charging.
1 − Record outdoor ambient temperature using a digital
thermometer.
2 − Attach high pressure gauge set and operate unit for
several minutes to allow system pressures to stabilize.
3 − Compare stabilized pressures with those provided in
table 7, Normal Operating Pressures." Minor varia-
tions in these pressures may be expected due to differ-
ences in installations. Significant differences could
mean that the system is not properly charged or that a
problem exists with some component in the system.
Pressures higher than those listed indicate that the
system is overcharged. Pressures lower than those
listed indicate that the system is undercharged. Verify
adjusted charge using the approach method.
12HPB24
Outdoor Coil
Outdoor Coil
Air Entering
liq.
Temp.
+10
_F (_C)
PSIG
65 (183.)
144
75 (23.9)
170
85 (29.4)
199
95 (35)
228
105 (40.6)
261
NOTE − Typical pressures only. Indoor evaporator match up, indoor air quantity, and evaporator load will cause the pressures to vary.
Normal Operating Pressures
12HPB30
vap.
liq.
vap.
+5
+10
+5
PSIG
PSIG
PSIG
78
140
76
79
164
77
80
194
78
81
224
79
82
259
80
4 − Use the same digital thermometer used to check out-
door ambient temperature to check liquid line tempera-
ture. Verify the unit charge using the approach method.
5 − The difference between the ambient and liquid temper-
atures should match values given in table 6. If the val-
ues don't agree with the those in table 6, add refriger-
ant to lower the approach temperature or recover re-
frigerant from the system to increase the approach
temperature.
Model
12HPB24
12HPB30
12HPB36
12HPB42
12HPB48
12HPB60
NOTE − For best results, the same thermometer should be used to check
both outdoor ambient and liquid temperatures.
Table 7
12HPB36
12HPB42
liq.
vap.
liq.
+10
+5
+10
PSIG
PSIG
PSIG
152
74
152
178
76
179
208
77
210
238
78
241
275
81
278
Page 15
Approach Method
Table 6
Approach Values
Liquid Temp. Minus Ambient Temp.
_F (_C)
6 (3.3)
11 (6.1)
12 (6.7)
10 (5.6)
9 (5)
8 (4.4)
12HPB48
vap.
liq.
vap.
+5
+10
+5
PSIG
PSIG
PSIG
75
146
75
76
171
77
77
198
78
78
229
79
79
268
81
12HPB60
liq.
vap.
+10
+5
PSIG
PSIG
146
73
175
74
206
75
237
76
275
77

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

12hpb2412hpb3012hpb3612hpb4212hpb4812hpb60

Table of Contents