Table 3. Maximum Undiluted Propane (LP) Delivery Capacity in Thousands of
BtuH (0.5" WC Pressure Drop) [Schedule 40 Metallic Pipe]
Pipe
10'
20'
Size
(3m)
(6m)
1/2"
291
200
3/4"
608
418
1"
1,150
787
1 1/4"
2,350
1,620
1 1/2"
3,520
2,420
2"
6,790
4,660
For reference only. Please consult gas pipe manufacturer for actual pipe capacities.
Final Check
When the installation is complete, verify that inlet gas pressure for the entire gas system does not
drop below 5" WC for NG or 8" WC for LP at all appliances. This can be tested by turning on all
gas burning appliances including the water heater, then check the inlet pressure at each appliance
to verify all appliances are receiving a minimum of 5" WC for NG or 8" WC for LP. If all appliances
are not receiving the minimum inlet pressure the gas piping system may need to be changed.
Length (including fittings)
30'
40'
50'
(9m)
(12m)
(15m)
160
137
122
336
287
255
632
541
480
1,300
1,110
985
1,940
1,660
1,480
3,750
3,210
2,840
CAUTION
60'
80'
100'
(18m)
(24m)
(30m)
110
101
94
231
212
197
434
400
372
892
821
763
1,340
1,230
1,140
2,570
2,370
2,200
125'
150'
175'
(38m)
(45m)
(53m)
89
84
74
185
175
155
349
330
292
716
677
600
1,070
1,010
899
2,070
1,950
1,730
200'
(60m)
67
140
265
543
814
1,570