Mitsubishi Electric MUZ-GF60VE-E1 Service Manual page 24

Outdoor unit
Table of Contents

Advertisement

11-2. FAILURE MODE RECALL FUNCTION
Outline of the function
This air conditioner can memorize the abnormal condition which has occurred once.
Even though LED indication listed on the troubleshooting check table (11-3.) disappears, the memorized failure details can be recalled.
1. Flow chart of failure mode recall function
for the indoor/outdoor unit
Operational procedure
The cause of abnormality cannot be found because the abnormality does not recur.
Setting up the failure mode recall function
Turn ON the power supply.
<Preparation of the remote controller>
While pressing both OPERATION SELECT button and TEMP
controller at the same time, press RESET button.
First, release RESET button.
Hold down the other 2 buttons for another 3 seconds. Make sure that the indicators on
the LCD screen shown in the right fi gure are all displayed. Then release the buttons.
Press OPERATE/STOP (ON/OFF) (MSZ-GF60/71VE) / STOP/OPERATE (OFF/ON)
(MSZ-GF60/71VE2) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit.
Does the upper lamp of OPERATION INDICATOR lamp on the
indoor unit blink at the interval of 0.5 seconds?
Blinks: Either indoor or outdoor unit is abnormal. Beep is
emitted at the same timing as the blinking of the upper
lamp of OPERATION INDICATOR lamp.
Judgment of indoor/outdoor abnormality
Before blinking, does the upper lamp of OPERATION INDICA-
TOR lamp stay ON for 3 seconds?
When it stays ON for 3 seconds (without beep):
The outdoor unit is abnormal.
The indoor unit is abnormal.
Check the blinking pattern, and identify the abnormal point by referring to the
indoor unit failure mode table. (Refer to indoor unit service manual.)
Make sure to check at least 2 consecutive blinking cycles.
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures.
Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.
Repair the failure parts.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function"
mentioned above.
Press OPERATE/STOP (ON/OFF) (MSZ-GF60/71VE) / STOP/OPERATE (OFF/ON) (MSZ-GF60/71VE2)button of
the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.
Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
Release the failure mode recall function according to "Releasing the failure mode recall function" mentioned
above.
NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
2. Blinking pattern when the indoor unit is abnormal:
Blinking at 0.5-
2.5-second OFF
second interval
ON
OFF
Repeated cycle
3.Blinking pattern when the outdoor unit is abnormal:
2.5-second OFF
3-second ON
ON
OFF
OBH635C
1
1. Regardless of normal or abnormal condition,
a short beep is emitted once the signal is
received.
2
Yes
(Blinks)
No
2
2.5-second OFF
second interval
Beeps
Repeated cycle
Blinking at 0.5-
second interval
No beep
Beeps
Repeated cycle
MSZ-GF60VE
MSZ-GF71VE
button on the remote
Indoor unit is normal.
But the outdoor unit might be abnormal because there are some abnor-
malities that cannot be recalled with this way.
No
Check if outdoor unit is abnormal according to the detailed outdoor unit
(OFF)
failure mode recall function. (Refer to 11-2.2)
Yes
The outdoor unit is abnormal.
Check the blinking pattern, and identify the abnormal point by referring to
the outdoor unit failure mode table. (Refer to 11-2.3)
Make sure to check at least 2 consecutive blinking cycles.
Blinking at 0.5-
Beeps
Repeated cycle
2.5-second OFF
3-second ON
No beep
Repeated cycle
24
MSZ-GF60VE2
MSZ-GF71VE2
3
Beeps
Blinking at 0.5-
second interval
Beeps
Repeated cycle

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents