Kohler TP-5353 Service Manual page 118

Industrial generator sets
Table of Contents

Advertisement

Governor Calibration for Paralleling
Generator Sets
Calibration Procedure
1. Place generator master switch to OFF. Generator
set must not be running.
2. Set the gain pot at 30% and the droop pot
completely counterclockwise (CCW).
3. Adjust the idle speed by turning the 20-turn pot
clockwise
(CW)
counterclockwise (CCW) to decrease speed.
4. Adjust the run speed by turning the 20-turn pot
clockwise
(CW)
counterclockwise (CCW) to decrease speed.
5. Place generator master switch to RUN or TEST
position to start generator set.
6. Slowly turn the gain pot clockwise (CW) until the
engine becomes unstable.
becomes unstable, slowly turn the gain pot
counterclockwise (CCW) until stable. Interrupt the
governor by momentarily removing power from the
governor.
The engine should recover in 3-5
diminishing oscillation. Stop the generator set.
TP-5353 8/94
to
increase
speed
to
increase
speed
After the engine
1. Place generator master switch to RUN or TEST
position to start generator set.
2. Use the run speed pot to set the engine rpm to the
desired no load speed (frequency) on the
frequency meter.
3. Apply full load to the generator set.
4. While watching the frequency meter, slowly turn
the droop pot clockwise (CW) until the desired
droop percentage is obtained.
5. Remove full load from generator set.
and
6. Using the run speed pot readjust the engine rpm to
the desired no load speed (frequency) on the
frequency meter. Stop the generator set.
and
Droop Adjustment