Indicator LEDs
Description
Normal
Charging (battery test not possible while charging)
Mains off, battery not connected or charger fault
Battery test
Battery fault
Light source test
Light source fault
Battery fault and light source fault
LED status explanation
On
Off
The OvaLED R Square Spot is a self-contained non-maintained luminaire with selftest function.

Selftest functions

Every 15 days the luminaire will perform an emergency operation test, this will light the white LED for
approx. 3 seconds. The red LED will flash during this test sequence.
Every 6. month the luminaire will perform a battery condition test. The test will last for 60 minutes. The
white LED will be lit and the yellow LED will flash during this test sequence.

Manual test functions

Manual tests can only be performed if both mains and battery are connected.
By pressing the test button briefly (less than 5 seconds) an emergency operation test is performed.
The white LED will be lit for approx. 3 seconds, the red LED will flash during this test sequence.
By pressing the test button for between 5 and 10 seconds a battery condition test is performed.
This test will last for 60 minutes and can only be performed when the battery is fully charged (steady
green LED). The white LED will be lit and the yellow LED will flash during this test sequence.

Resetting errors

Push the test button for >10 seconds to delete all indicated errors. Then the luminaire enters regular
operation mode.
In case that the luminaire no longer meets its rated duration of operation, the battery must be replaced
(see chapter "Battery replacement" on previous page).
Flashing
Technical description
Part number:
Lumen output:
Operation voltage:
Emergency mode duration:
Battery:
Battery protection:
Charging time:
Maximum power consumption:
Ambient temperature range:
Relative humidity:
Weight:
Classification:
IP20
Expected battery lifetime 4 years
At the end of their useful life the
packaging, product and batteries
should be disposed of via a
suitable recycling centre. Do not
dispose of with your normal
household waste. Do not burn.
Note:
In case of mains power disconnection for a
period of more than two months, the battery
must be disconnected.
Note:
In case of battery replacement, this must be
replaced with parts of the same type
.
characteristics
The replacement must be performed by the
manufacturer or a competent person.
GB
290173
156 lm
220-240VAC 50/60Hz
Minimum 1 hour
4,8V / 1,2Ah NiMH
Overcharge and full discharge
13 hours
3W / 3,5VA
5 to 40°C
Up to 95%
435 g
EN 60598-2-22
and