Selkirk CF Sentinel Installation Instructions Manual

Selkirk CF Sentinel Installation Instructions Manual

Factory-built insulated chimney

Advertisement

Model CF
(6" to 8" dia.)
FACTORY-BUILT
INSULATED CHIMNEY
LISTED
Tested to Standard
CAN/ULC-S629
&
UL 103 Type HT
2021 CF Sentinel
Installer: It is of the utmost importance that these instructions are
Homeowner: Keep these instructions and maintenance guide in a safe
1
A MAJOR CAUSE OF
CHIMNEY RELATED FIRES IS
FAILURE TO MAINTAIN
REQUIRED CLEARANCES
(AIR SPACES) TO COMBUSTI-
BLE MATERIALS.
IT IS OF THE UTMOST
IMPORTANCE THAT THIS
CHIMNEY SYSTEM BE
INSTALLED ONLY IN
ACCORDANCE WITH THESE
INSTRUCTIONS.
PLEASE READ ALL INSTRUCTIONS
BEFORE BEGINNING YOUR
INSTALLATION.
FAILURE TO INSTALL THIS SYSTEM IN
ACCORDANCE WITH THESE
INSTRUCTIONS WILL VOID THE
CONDITIONS OF CERTIFICATION AND
THE MANUFACTURER'S WARRANTY.
left with the homeowner.
place for future reference.
3009214
I
I
NSTALLATION
NSTRUCTIONS
&
M
G
AINTENANCE
UIDE
SELKIRK CANADA CORPORATION
950 South Service Road, Second Floor
Stoney Creek, ON L8E 6A2
1-888-SELKIRK (735-5475)
Fax: 1-866-835-9624
www.selkirkcorp.ca
cscanada@selkirkcorp.com
02/12/21

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CF Sentinel and is the answer not in the manual?

Questions and answers

Dave
January 25, 2025

Can a Selkirk 6inch be installed outside of house with a 12 inch overhang on the roof witch would require an offset

1 comments:
Mr. Anderson
February 10, 2025

The Selkirk CF Sentinel chimney allows offsets but limits them to no more than 30 degrees. Additionally, two pairs of 15 or 30-degree elbows may be used per interior installation. However, the manual strongly recommends installing the chimney within the building in cold climates to prevent operational issues like poor draft and excessive condensation. If installed on an exterior wall, enclosing the chimney below the roofline is advised to protect it from cold temperatures. Given these guidelines, a 6-inch CF Sentinel chimney can be installed outside with an offset to clear a 12-inch roof overhang, as long as the offset does not exceed 30 degrees and follows the required installation practices.

This answer is automatically generated

Summary of Contents for Selkirk CF Sentinel

  • Page 1 Homeowner: Keep these instructions and maintenance guide in a safe place for future reference. UL 103 Type HT SELKIRK CANADA CORPORATION 950 South Service Road, Second Floor Stoney Creek, ON L8E 6A2 1-888-SELKIRK (735-5475) Fax: 1-866-835-9624 www.selkirkcorp.ca cscanada@selkirkcorp.com 2021 CF Sentinel 3009214 02/12/21...
  • Page 2: Table Of Contents

    TABLE OF CONTENTS CERTIFICATION LABELS TYPES OF APPLIANCES PRE-INSTALLATION GUIDELINES TOOLS CF SENTINEL JOINT SECURITY FRAMING DETAILS CEILING SUPPORT INSTALLATION SMOKE PIPE ADAPTER 6, 7 FIRESTOP JOIST SHIELD 7, 8 ATTIC INSULATION SHIELD INSTALLATION 8, 9 ELBOW INSTALLATION WALL SUPPORT INSTALLATION...
  • Page 3: Certification Labels

    CERTIFICATION LABELS...
  • Page 4: Types Of Appliances

    UL 127 and CAN/ULC-S610 when specified in the fireplace manufacturer's installation instructions. U.S.A. APPLICATIONS The CF Sentinel chimney has been tested per UL-103 as "Type HT". As such it is code approved for connection to solid, liquid EAR SAFETY GLOVES WHEN HANDLING...
  • Page 5: Tools

    (see Figure 3B). Lift the clasp with a screwdriver if TOOLS necessary. Your CF Sentinel chimney system is designed for installation 3. When a chimney section is suspended e.g: below a Cathedral using standard building materials and procedures. The following...
  • Page 6: Ceiling Support Installation

    Adapter must be inserted into the female end of the first length ney. (see Figure 9a). The CF Sentinel Ceiling Support will support up to 40 feet (12.2m) - Insert the short portion of the short crimped Smoke Pipe Adapter of chimney sections, all of which must be installed above the into the Basecap.
  • Page 7: Firestop Joist Shield

    Ensure that the Chimney Length rests on the Lower Bucket into the Ceiling Support (see Figure 9c). NOTE: Any length of CF Sentinel Chimney can be used. There is no special "Starter" length required with the Ceiling Support. Make sure the length is long enough to be...
  • Page 8: Attic Insulation Shield Installation

    Fully frame a level square opening (all four sides) for 2" ( 50mm) clearance from the outside of the chimney to the inside of the Round Top frame. Place the Firestop Joist Shield (JS) up into the framed FIGURE 13 opening from below the joist framing and nail in place using 1"...
  • Page 9: Elbow Installation

    NOTE: At the level where the chimney penetrates the air / vapour The maximum permissible angle with solid fuel CF installation is 30 barrier, special attention is required. Seal the vapour barrier to the degrees. Combining offsets for greater angle is not permitted. The Ceiling Plate of the Ceiling Support, Wall Thimble or Attic vertical run of chimney above an offset must be supported using an Insulation Shield using an appropriate caulking compound as per...
  • Page 10: Wall Support Installation

    - Round Top: - To exclude rain and/or leaves into the chimney. Wall Band The CF Sentinel Adjustable Wall Support will support up to 40 feet (12.2 m) of chimney, all of which must be above the support. Locking Band 1.
  • Page 11: Wall Band

    Wall Thimble or a concrete wall. 2. Clamp the two halves of the support band around the chimney 11. NOTE: Only CF Sentinel chimney must extend through-the- pipe using the long bolts through the band end tabs. First install wall. Use the Wall Plate Spacer (or the interior portion of the the pivot screws.
  • Page 12: Cathedral Ceiling Support Installation

    Roof Flashing - Round Top:- To exclude rain and/or leaves into the chimney. 50mm (2") Minimum Air The CF Sentinel Cathedral Ceiling Support will support a total of Space Clearance May be installed flush on 15 feet (4.6m) of chimney, of which 10ft (3m) can be supported below...
  • Page 13 To Install: 7. Center the assembly in the opening. Adjust Plates to the 1. Place the two halves of the URSA Band as shown in Fig.24. pitch of the roof and tighten the nuts (see Figures 25b & 26). Insert elevator bolts through the single row of holes identified with the outside diameter of the chimney being installed, (Ex.
  • Page 14: Roof Flashing Installation

    This will extend its life and improve the appearance. Large The chimney may be painted also with a HEAT RESISTANT Washer Elevator bolt for paint. To improve adhesion to the CF Sentinel chimney, degrease, Telescoping Legs clean, prime before painting. Follow the paint manufacturer's Lock Washer Through Appropriate Holes of both halves instructions.
  • Page 15 G. Attach each of the telescoping legs (angled end) to the 2 elevator bolts on the Support Band with supplied washers Elevator Support Band and nut (see Figure 33). Halves Bolt H. Attach one end of each telescoping leg assembly to each of the Angle Brackets using one (1) 1/4-20 X 1”...
  • Page 16: Round Top

    NOTE: Do periodic inspection of all fasteners including the hose SPARK ARRESTER (SA) clamps as high winds can cause the chimney system above the Use a spark arrester if you have a shingle roof or live in a forested roof to vibrate and in time loosen some of the fasteners. area.
  • Page 17: Maintenance And Cleaning Of Chimney

    CHIMNEY FIRES AND WHAT TO DO ABOUT THEM When wood is burned slowly, it produces tar and other organic Your CF Sentinel chimney is not intended or designed for use as vapors, which combine with expelled moisture to form creosote.
  • Page 18: Replacement Parts List

    BURN ONLY SEASONEDFIREWOOD! REPLACEMENT PARTS LIST Wood burns completely only at very high temperatures with enough oxygen present. The fuel, heat, and oxygen have to mix together in the same place at the same time. Although all DESCRIPTION PART N stages of burning wood actually occur at the same time, it will burn in 3 stages: boiling off the water, vaporizing wood gases SENTINEL CF...
  • Page 19: Anchor Plate For Masonry Fireplace

    Combustibles - Smoke Pipe Adaptor All Masonry or Steel Shell Model CF Sentinel Anchor Plate provides a connection from a masonry fireplace to a Selkirk Model CF Sentinel chimney. The following steps describe the installation of this part (component) and the above mentioned sections of these instructions are to be followed.
  • Page 20: Chart 1 - Offset Chimney Installation

    CHART 1 - OFFSET CHIMNEY INSTALLATION When the chimney path cannot be perfectly straight, the need to install a chimney offset must be used when it becomes necessary to offset the chimney in order to clear a joist or an obstacle. The two (2) charts below will assist you in selecting the proper combination of elbow angle and chimney length(s) that will provide the necessary degree of offset within an available height.
  • Page 21: Chart 2 - Chimney Height Above Roof

    CHART 3 - Connector Pipe Clearance below Cathedral Support 1. Identify the type of connector pipe you will be installing, single wall (requires 18" clearance to combustibles) or Selkirk's Double Wall Stove Pipe (model DSP) which requires 6" clearance to combustibles.
  • Page 22: Installation Record

    INSTALLATION INFORMATIONSTALLATION INFORMATI Leave with homeowner. Homeowner: Keep in a safe place for future reference. PRODUCT INFO CF Sentinel CHIMNEY MODEL : FLUE SIZE________ TOTAL HEIGHT_________ INSIDE INSTALLATION OUTSIDE INSTALLATION CONNECTED TO (type of appliance): WOOD STOVE BOILER FURNACE LISTED FACTORY-BUILT FIREPLACE...