Deciding on Where to Install the Air Conditioner (Continued)
N MH070FXEA4B/MH080FXEA4B
Indoor unit
✴✴026/030/035/052✴✴
C C
A A
U U
T T
I I
O O
C C
A A
U U
T T
I I
O O
3m as minimum pipe length. It will reduce noise
and vibration.
If just one indoor unit is connected this value
must be increased up to 7.5m.
300 mm
minimum
600 mm
minimum
◗ Piping length and the height
Dimension
Composition
◗ System can work with one indoor unit connected,but it is recommended that the TOTAL number of
indoor unit suggested by manufacturer are connected to obtain the maximum performance.
❊ The appearance of the unit may be different from the diagram depending on the model.
8
E-
Power supply
Outdoor unit
Ø, V, Hz
MH070FXEA4B
1, 220-240, 50
MH080FXEA4B
N N
N N
600 mm
minimum
300 mm
minimum
1 Room max
4 Room total max
length
25 m
A, B, C, D
Make at least one round :
It will reduce noise and vibration.
◗ Piping outside diameter
Outside diameter
Unit
Liquid
✴✴026/030/035✴✴
1/4"
✴✴052✴✴
A
B
Main power switch
Max height between
length
indoor unit & outdoor unit
70 m
15 m
A + B + C + D
(H)
Gas
3/8"
1/2"
(h)
C
D
Max height between
indoor units
7.5 m
(h)
(H)