System Specifications; Derating The Burner; Locating The Fireplace - Alpine SERRANO SE36-NG Installation And Operating Instructions Manual

Positive pressure gas fireplace
Table of Contents

Advertisement

GENRAL INFORMATION/INSTALLATION REQUIREMENTS

SYSTEM SPECIFICATIONS

Burner Inlet Orifice Sizes:
(2500 TO 6500 feet altitude )
Natural Gas: #40
Max. Input Rating –
Min. Input Rating –
Min. Supply Pressure
Max. Supply Pressure
Manifold Pressure
Natural Gas
Propane
Minimum Gas Line Pipe Size: 1/2"
Electrical: 120 V.A.C. System
Amperage Rating: 3.25 /3.50 Amps
Positive Pressure Fan: Variable Speed 495 CFM.
Venting: Simpson Duravent Direct Vent (4" x 6 5/8")
Must use high wind termination on vertical
applications (Simpson part # 0991)
This appliance may be installed in an aftermarket, perma-
nently located, manufactured home (USA only) or mobile
home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated
on the rating plate. This appliance is not convertible with
other gases, unless a certified kit is used.

DERATING THE BURNER

The fireplace has been designed to operate at elevations up
to 4500 ft. above sea level. The fireplace will need to be
derated at elevations above 6500 ft. The orifice will need to
be reduced one number drill size.
6
Propane: #52
Natural Gas
31,000 Btu/h
Propane
33,000 Btu/h
Natural Gas
23,000 Btu/h
Propane
25,000 Btu/h
Natural Gas
4.5" w.c.
Propane
11.0" w.c.
Natural Gas
8.0" w.c.
Propane
13.0" w.c.
3.5" +/-0.2" w.c.
10" +/-0.2" w.c.
Alpine SE36 Direct Vent Gas Fireplace

LOCATING THE FIREPLACE

1) When selecting a location for your Gas Fireplace,
ensure that the clearances outlined in this manual are
adhered to strictly.
2) Ensure that the Positive Pressure Blower will be
accessible for post-installation maintenance.
3) The fireplace must be installed on a flat, solid,
continuous surface. If the appliance is to be raised
off the floor on a platform, it must be securely
fastened to a sturdily constructed platform.
4) If the appliance is to be installed on carpeting,
combustible vinyl tiling, or any other combustible
surface other than wood flooring, a wood panel or
metal panel must be installed on top of the existing
flooring. The panel must extend the full width and
depth of appliance.
5) The Alpine SE36 fireplace can be installed into
many different applications. See Figure 1 for
examples.
6) Lay out fireplace dimensions on installation site
before proceeding with installation. This will ensure
proper clearances and assist in identifying potential
problems before installation.
7) Make sure to review the vent termination and
positive pressure system requirements before
proceeding.
Fig. 1 – Installation Placement Options