Page 1
BMPC/2 Bruker Magnet Pump Control 2 Technical Manual Version...
Page 2
Manufacturing Location: Bruker BioSpin SAS France 34, rue de l‘industrie 67166 Wissembourg Cédex France For further technical assistance on the BMPC/2 unit, please do not hesitate to contact your nearest BRUKER dealer or contact us directly at: BRUKER Corporation am Silberstreifen...
Page 6
Faulty Flow Meter Readings................130 14.5 Replacement of the Sub-Cooling Pumps Inside the BMPC ........ 130 14.5.1 Replacement of the sub-cooling Pumps inside the standard BMPC/2 MC5300 . 131 14.5.2 Replacement of the sub-cooling Pumps inside the Aeon BMPC/2 M136266..134 14.5.3 Replacement of the Three-phase Sub-cooling Pumps inside the Double-Rack BMPC 14.6...
For older hardware, please refer to the manual supplied at the time. Policy Statement It is the policy of Bruker to improve products as new techniques and components become available. Bruker reserves the right to change specifications at any time.
Page 8
WARNING This combination of symbol and signal word indicates a potentially hazardous situa- tion which could result in death or serious injury unless avoided. CAUTION This combination of symbol and signal word indicates a possibly hazardous situation which could result in minor or slight injury unless avoided. NOTICE This combination of symbol and signal word indicates a possibly hazardous situation which could result in damage to property or the environment unless avoided.
Control 2 (BMPC/2). To maximize reliability and up-time, the BMPC/2 features redun- dancy of several components of the sub-cooling technology, most importantly the sub- cooling pump. As the pump is subject to wear, BMPC/2 operation is based on an appro- priate backup and a cyclic replacement scheme.
In addition to the monitoring and control of the pump system the BMPC/2 also monitors the magnet status and the main cryogenic system parameters. The monitoring system also features an alarm function. The main functions include: • Monitoring of the magnet status and the most important cryogenic system parame- ters.
(Administrator)" on page Alarm and Notification System An integral part of the BMPC/2 system is the Alarm System and Voice Box System. The Alarm System is needed for the supervision of the magnet system. A description of this system is available in the chapter "Alarm System"...
NOTICE To avoid switching off the device by accident the BMPC/2 circuit breaker is not directly accessible for the user. The circuit breaker of the UPS unit can be used to switch off the BMPC/2 unit.
If you have questions about how to use the BMPC/2, please contact the supplier. NOTICE Please keep this manual for future use. Safe Handling of Cryogenic Substances NOTICE The BMPC pumps gaseous helium at room temperature from the magnet. The pumped helium is expelled into the atmosphere, into a helium recovery system, or, in case of Aeon systems, circulates in a closed loop.
Analog Telecommunication Safety NOTICE Analog Telecommunication Safety Warnings Before servicing, disconnect this product from its power source and telephone net- work, and adhere to the following safety warnings: Never install telephone wiring during a lightning storm. Never install a telephone jack in wet locations unless the jack is specifically designed for wet locations.
Circuit protection Frequency 50 - 60 Table 4.2: Electrical Connection Values Site Conditions The BMPC/2 should only be used: • In a standard laboratory environment. • Up to a maximum elevation of 2000 meters. • At a temperature between 15-35 °C.
Power Input Safety Fuse The power input safety fuse for the BMPC/2 is a 40A dual-element time delay fuse Class J 600V. The Bruker part number for this fuse is 87159. Two fuses of this type are used in the unit.
RS232 MODE PUMP 1 VALVE12 PUMP 2 VALVE 2 PUMP 2 AUTO OPEN OPEN OPEN MANUAL CLOSED BMPC/2 CLOSED CLOSED T1, T2. Compressor BMPC/2 V1 V2 Pmp1 Pmp2 LHe Level RS232 230V 230V UPS Status Ethernet TopSpin 230V 50/60 Hz NMR Console Figure 5.2: System Block Diagram Magnet Systems for Sub-Cooled Magnet Systems with Helium...
Internal UPS Pump Cabinet Pmp2 Pmp1 Figure 5.3: General Structure of the BMPC/2 Magnet Pump Control for Non-refrigerated Systems 5.2.1 TFT Display The system utilizes a standard 19" TFT display with a resolution of 1280 x 1024 pixels. The display also includes a 2 port USB hub for use with accessories.
5.2.2 BMPC/2 Control Unit The BMPC/2 Control Unit (P/N H13029) consists of the following main components: Component Description BMPC/2 Manual Control This board (P/N H13024) is used for manual control of the Board pumps and valves. BMPC/2 Automatic Control This Board (P/N H13022) is used to fulfill the following functions: Board •...
• A helium flow meter (FM, see table below) which measures the helium flow at the exhaust of both pumps. The flow meter is connected to the BMPC/2 control unit via the CAN bus. • A temperature sensor (PT100) to measure the temperature T5 inside the pump cab- inet.
BMPC/2 are part of this unit. The line control unit is located in the upper rear part of the BMPC/2. To access the line control unit, you have to open the upper rear door using a screwdriver to turn both screws (quarter turn to the left).
V2, V3, KM10, KM13 KM6, KM7, KM8, KM16, KM18, KM20 Current Sensor KM12, KM15 Main Switch I1 Time Delay Contactor Enable Main Input Console Off Console KM4 Console Fuse FU1, FU2 Switch S4 Figure 5.5: BMPC/2 Line Control Unit Z31823_00_08...
BMPC/2 Wiring Box The BMPC/2 Wiring Box (P/N H13030) is mounted on a flange in the upper region of the magnet. It is designed as a CAN BUS slave and connects the BMPC/2 to the tempera- ture sensors T1 and T2 and to the heater resistors for H1 and H2. The wiring box also contains a small LC display where the main magnet parameters and system messages can be viewed.
All sensors and the BMPC/2 wiring box are designed as CAN bus slaves. The BMPC/2 wiring box is also able to fullfill CAN bus master functions in case the BMPC/2 control unit is not functioning.
NMR Console 86490 86490 provided from Console Figure 5.8: External Wiring Overview for use with NMR Spectrometers TFT - Display Mains HZ13576 BMPC/2 Control Unit HZ13576 PC Keyboard Line Control Unit (shown form rear side) Industrial PC 87496 HZ13723 Mains...
Connection to X1 of Line Control Unit Mains Input Connection to X2 of Line Control Unit 110-230V PT100 RS-232 to IPC 50/60Hz Wiring Box Power RS-232 to NMR Console/AV4 Retrofit RS-232 BMPC Kit Figure 5.10: BMPC/2 Control Unit Rear Panel Z31823_00_08...
The internal 1kVA 19” Rack Mount UPS is used to protect the Industrial PC against downtime, data loss and helps to send alarm faxes and alarm calls in the case of an power failure for a time of 15-30 minutes. Bruker P/N 1802515 - POWERWARE PW9130G-1000R-XL2UEU (UL listed) Mains Input USB Connection to IPC...
5.6.5 Main UPS The main UPS of the BMPC/2 is located outside the housing of the BMPC/2. It com- prises the actual UPS module and the UPS extension module (P/N 1855601). The apro- priate UPS module depends on the region where it is used: For Europe and other 50Hz regions: •...
5.6.6 Line Control Unit 5.6.6.1 Connectors to External Devices/Units Figure 5.14: Line Control Unit Connector X3 / X4 / X5 Connector X3 Neutral Line 2nd PE Connection Values Mains Input 230 V 50/60 Hz Console Output 230 V 50 Hz 4 kW Table 5.4 Pinout of Connector X3 (External Connectivity) Connector X4...
Connector X5 Relay Contacts Connection Values PTC Remote (not used) 6/12 6 A 230 V AC Alarm 1 4/10 6 A 230 V AC Alarm 2 5/11 6 A 230 V AC Table 5.6 Pinout of Connector X5 (Part One: External Connectivity) Output Neutral Line...
5.6.6.2 Connector X6 UPS Status Interface Connection to UPS Status Interface Figure 5.15: Picture of Connector X6 Pin Number Pin Function Not connected Not connected General alarm (normally opened) On commercial AC (normally closed Ground UPS on bypass (normally opened) Battery low (normally opened) UPS present (normally closed) Not connected...
Transport, Packaging and Storage Symbols on the Packaging The following symbols are affixed to the packaging material. Always observe the sym- bols during transport and handling. The arrow tips on the sign mark the top of the package. They must always point upwards; otherwise the content may be damaged.
Page 38
Attach Here Lifting gear (lifting chain, lifting strap) must only be attached to points bearing this symbol. Center of Gravity Marks the center of gravity of packages. Note the location of the center of gravity when lifting and trans- porting. Weight, Attached Load Indicates the weight of packages.
Component Sensitive to Electrostatic Discharge (EDS) The packaging contains components which are sensitive to an electrostatic discharge. Only allow packaging to be opened by trained personnel. Establish potential equalization before opening. Protect from Heat Protect packages against heat and direct sunlight. Protect from Heat and Radioactive Sources Protect packages against heat, direct sunlight and radioactive sources.
Packaging About Packaging The individual packages are packaged in accordance with anticipated transport condi- tions. Only environmentally friendly materials have been used in the packaging. The packaging is intended to protect the individual components from transport damage, corrosion and other damage prior to assembly. Therefore do not destroy the packaging and only remove it shortly before assembly.
The operation of the pumps and valves in manual mode takes place with the help of the different buttons located on the front plate of the BMPC/2 control unit. The function of these buttons, which are illustrated in the following diagram, will be discussed in the fol- lowing sections.
7.1.1 Mode Buttons The mode buttons are used to switch between manual and automatic pump mode. To enter automatic pump mode press the AUTO mode button. The green lamp will acti- vate when the unit switches to automatic mode. To return to manual mode press the MANUAL button. The green light will deactivate and the red lamp will activate indicating that the unit is in manual mode.
However, when the BMPC/2 software is operating in Monitor & Alarm mode, you will nevertheless be alarmed when important magnet parameters exceed or fall below their limit values. Always place the BMPC/2 software in Monitor & Alarm mode when working in manual mode. Z31823_00_08...
Refer to the section "Monitor & Alarm Mode" on page 60 for more information on the BMPC/2 software. Automatic Pump Mode NOTICE Valve 3 should be closed if the helium flow rate is greater than 1.5 times the normal rate.
7.3.1.1 Default Pump Failure The BMPC/2 continuously monitors the condition of the default pump(s) in operation. If one of the pumps or valves malfunctions: The malfunctioning pump (or valve) and its corresponding valve (or pump) are stopped or closed. Either the other pump switches on automatically and the corresponding valve is opened, or, when both pumps were operating, the other pump will continue to oper- ate and its corresponding valve will remain open.
7.4.2 T1/T2 Temperature Monitoring The T1 and T2 temperatures are continuously monitored against a pre-specified lower limit and the following actions taken if the limit is reached: Precondition Condition Action The resistance of the tem- Backup pump is started and perature sensor T1 or T2 a warning is triggered.
Starting the BMPC/2 Software To start the BMPC/2 Control software you will need to enter your account ID and pass- word and press Enter. The account ID and password can be delegated from the Admin- istrator or Bruker Service.
Figure 8.1: BMPC/2 Login Screen Program Overview The software interface consists of five different "Display Modes": • Process Display • Graphical Display • Jumbo Display • Data Log Display • Present Values/Events Display The interface also has four different "Operation Modes":...
Display Mode Buttons Operation Mode Buttons Info. Menu Bar Tool Bar Selected Display Status Bar Current Login Current Mode Current Status Activity Indicator Figure 8.2: Display Organization The top of the screen contains a standard Windows menu bar. Just under this is a tool bar which contains buttons providing quick access to the five different display modes, the four operation modes, as well as system information.
The process display is the default display in display mode. The most important magnet and BMPC/2 parameters are indicated in a representative process image. Thus, a cor- relation of the parameters to their functions is available at any given time.
Figure 8.5: Process Display with Compressor 8.3.2 Graphical Display The graphical display allows you to plot arbitrary parameters on a timeline. Up to 3 differ- ent graphs can be represented simultaneously on the display screen. The graphical dis- play is freely configurable based on specific needs. Z31823_00_08...
Configuration Graph 1 T1 and T2 Graph 2 P2 and P3 Figure 8.6: Graphical Display In the example above is a configuration for two graphs. The settings for both graphs are identical. In both examples data for the last 30 days is represented. Whenever new data is added to the log file the graphical display is automatically updated (refreshed).
8.3.2.1 Configuration of the Graphical Display At the top half of the graphical display are several checkboxes and fields that can be used to configure the graphical display representation to your individual needs. By selecting or deselecting checkboxes and/or entering parameters you can specify your requirements.
• Filtered display: If you want to view the data within a certain timeframe, you can do so by entering a beginning and ending date. The adjustments that have been made will automatically be used for all the other graphs when you click on the "Use these parameters for all graphs"...
to get this result: Zoom into this selection Figure 8.9: Graphical Display - Zoom Function 8.3.3 Jumbo Display In Jumbo display mode you can display up to 5 parameters using an extra large font size. This is useful if you want to read the displayed values when you are at a greater distance from your monitor.
Figure 8.10: Jumbo Display 8.3.3.1 Configuration of the Jumbo Display To activate or deactivate parameters displayed in the Jumbo Display press the corre- sponding channel button (e.g. T1, T2, etc.). These channels have been selected to display in the Jumbo Display Figure 8.11: Jumbo Display Configuration The buttons that are grayed out are the parameters that are currently displayed using the extra large font size in the Jumbo Display window.
8.3.4 Data Log Display The Data Log display is in the broadest sense a database browser. In this display you can display all the parameter data that is stored in the database. Figure 8.12: Data Log Display To activate or deactivate a specific parameter press the corresponding channel select button.
BMPC/2 Control Unit, PTC Compressor (optional), BMU (optional) or HLMU (optional). The Event log filter buttons on the upper part of the display allow you to select data that is relevant for your purposes.
8.4.2 Monitor Only Mode In this mode the current values of all magnet and BMPC/2 data are displayed, but the alarms are deactivated. The data is saved in the Data Log File when operating in this mode.
8.4.3 Monitor & Alarm Mode In this mode current values of all magnet and BMPC/2 data are displayed, and the alarms are activated, whereas you will be informed if a malfunction occurs. The data is saved in the Data Log File when operating in this mode.
8.4.4 He Fill Mode The He Fill mode is necessary because the T1 and/or T2 parameters may briefly fall below the alarm threshold during the helium refill process. In order to avoid an alarm from being triggered the He Fill mode can be used to suppress the T1/T2 alarm for up to six hours.
To prevent false alarms during the automatic pump test, all alarms are temporarily dis- abled. The automatic pump test is only possible if the BMPC/2 is running in automatic mode! 8.5.1 Description of the Test Cycle The automatic pump test consists of the following series of events: The backup pump is switched on.
8.5.2 Configuring the Automatic Pump Test The automatic pump test can be configured to start at a pre-designated date and time. To configure the automatic pump test: Select the OFF mode in the menu bar. Select Tools - Options - Pump Control - Pump Test Check the "Enable Automatic Pump Test"...
Figure 8.20: Event Log - Pump Test 8.5.3 Manual Start of the Pump Test It is also possible to check the function of the backup pump manually. To start the pump test manually: Select the OFF mode in the menu bar. Select Tools - Options - Pump Control - Pump Test.
Figure 8.21: Tools - Options - Control Unit - Pump Test If the automatic pump test is disabled, a faulty backup pump will not be recognized. Thus when the main pump fails there will be no backup pump which could lead to instabilities of the magnet.
Alarm System The alarm system is an important part of the BMPC/2 and is needed for the supervision of the magnet system. The alarm system uses an analog telecommunication network, based on an analog fax modem (with its own modem controller), and normally is avail- able for use worldwide.
An alarm will also be triggered if the communication between the industrial PC and the BMPC/2 Control Unit (RS232) fails. This may occur, for example, when a power failure occurs, which lasts longer than the backup time of the external UPS, or which is not pro- tected by the external UPS.
Alarm Groups 9.4.1 Internal Group Only company internal phone numbers should be assigned to the "Internal Group”. Typ- ically, during the week, the likelihood of reaching someone in the "Internal Group” is high so a response to the alarm should be very fast. Depending of the configuration it may need more than one loop through the "Internal Group”...
10.1 Alarm Call from the BMPC/2 When an alarm sequence is activated, the voice box system calls all the telephone num- bers on the internal and the external phone list (also see "Contact List"...
It is possible to request a status report at any time from any place in the world via a touch-tone phone. To do so: Dial the telephone number of the BMPC/2 modem. Wait for the message greeting. When queried, press the star button.
After selecting the period for the fax report, the user will be requested to type in a fax number. There are three options available: You can type in the fax number where you want to receive the status report using the international phone number format (i.e.
The subject line of the e-mail will start with ‘[BmpcEmail#<three digit number>]. This number is a specific ID (i.e. BRUKER service engineer). This ID is used by BRUKER e- mail server to forward the incoming e-mail to the person who has requested the e-mail.
Recalibrate the temperature sensors for T1 and T2. • Perform CAN bus diagnostics. To use the setup tool, first stop and close the BMPC/2 control program. 11.1 Starting the Setup Tool The setup tool requires administrator rights. Starting of the setup tool therefore will only proceed after acknowledging the user account control.
PL_100201v5.0.H86 has the release date of February 1, 2010, and Version 5.0. When the BMPC/2 is started, it checks if the version V5.0 corresponds to the internal stored version Vx.y. If the major release value ("x") is equal, the software will start, otherwise a warning window will appear and the software will not start.
In the above example a communication problem with the flow meter was detected. If the test fails, read the section "When the Value of a Parameter is Displayed as NAN" on page 130 for tips on handling this problem. If this does not help contact Bruker ser- vice for assistance. Z31823_00_08...
This function is used to recalibrate the temperature sensors for T1 or T2. To use this function you need both calibration connectors BMPC/2 T1/T2 Calibration Connector High (P/N HZ13703) and BMPC/2 T1/T2 Calibration Connector Low (P/N HZ13704). Start the calibration by selecting the Calibrate Temperature Linearization Function.
12 Configuration (Administrator) The configuration of the BMPC/2 is limited to the Administrator and Bruker service per- sonnel. For optimal operation of the BMPC/2 several system parameters must be adjusted. In addition, some local adjustments are needed concerning the telephone system that is used and the error alerts that are required.
Select your magnet from the pull-down list. Enter the temperature measuring resistance for T1 and T2. The limit data is then calculated automatically. Press the Next button to continue to the next magnet setup step. Setpoint for P2 Resistance Value for Heater 1 and for Heater 2 Figure 12.2: Magnet Setup Step 2...
12.2 Customer Setup Wizard The telephone system, modem adjustments and alarm system for the BMPC/2 can be configured using the Customer Setup Wizard. Important: The Customer Setup Wizard will overwrite the previous setup! To start the wizard select Tools - Customer Setup from the main menu.
Figure 12.4: Customer Setup - Contacts List (alarm) When you desire that an additional fax (in addition to Bruker Germany) be sent in case of an alarm, enter the fax number in the space provided. The four responsible individuals should be able to carry out the necessary steps required to stabilize the system in the event of a malfunction.
12.2.3 Alarm Groups Figure 12.5: Customer Setup - Alarm Groups The Alarm Groups have already been pre-configured. Press the Next button to continue to the Fax Setup. Z31823_00_08...
12.2.4 Fax Setup - Fax ID Figure 12.6: Customer Setup - Fax Setup - Fax ID Enter the name of your company or institution. Enter the appropriate fax number for the sender. These entries serve for the identification of the fax and do not influence the fax dis- patch.
12.2.5 Fax Setup - Fax Header (System) Figure 12.7: Customer Setup - Fax Setup - Fax Header In this window you will be required to enter all the data related to your magnet system. When an alarm or status fax is sent this information will appear in the header of the fax, as indicated in the red marked area of Figure 12.7:.
Enter the individuals responsible for the magnet system in the space provided. In the event of an alarm, Bruker can only provide effective assistance if all the informa- tion in the customer data header is valid and current.
Customer Setup - Fax Setup - Fax Header (Bruker) Figure 12.9: Customer Setup - Fax Setup - Fax Header (Bruker) Enter the data for your local Bruker office in the upper fields of the setup window. In the lower fields enter the necessary information concerning the service engineer who installed the system.
12.2.8 Customer Setup - Summary Figure 12.10: Customer Setup - Summary Verify the information in the summary for accuracy and completeness. If the information is correct press Finish to complete the setup, or Back to correct any setup data. Z31823_00_08...
12.3 The Options Menu The Options Menu allows you to make basic adjustments to the BMPC/2. The adjust- ments that are allowed are based on the login level. You need to login as an administra- tor to make changes using the Tools - Options menu.
Figure 12.12: Tools - Options - Passwords & Codes User Password When you are logged in as a normal user you are able to control the BMPC/2. You are also allowed to change between the different displays and to select between the operat- ing modes.
If you have changed a password which was used by another person, do not forget to inform them about the changes! 12.3.1.2 Communication Settings Figure 12.13: Tools - Options - Communication Settings The default value for the Com Port is "1". The other communication parameters are only displayed for information purposes, they cannot be changed.
Changes should only be made by experienced personnel that understand the implications of these changes. When you want to change a limit value, first select the parameter, then enter the new upper and lower limit values. To transfer the new values to the BMPC/2 press the Write Values button. Selected Parameter Figure 12.14: Tools - Options - Limit Values...
Read Values: Pressing this button will result in the display of the current values from the BMPC/2. This is useful when you have changed the values, but not written them to the unit and want to reload the current values.
Page 94
• Heater Mode: It is possible to operate in automatic or manual heater mode. As default Automatic mode is selected. In automatic mode, internal regulation ensures that the P2 pressure remains constant in the magnet dewar, based on the values entered.
12.3.2.3 Control Unit This option window allows you to read the current firmware version from the BMPC II, and to reset the control unit. Figure 12.16: Tools - Options - Control Unit A software reset may be necessary when, during a system start or a firmware download, communication to various sensors does not start correctly.
12.3.3 Monitoring System 12.3.3.1 Sensor Channels In this settings window you can configure the effect of the individual sensor channels on the alarms, as well as the representation of the channels in the various display options. Selected Sensor Channel Row in Present Value Display Channel Active Column in Data Log Display Enable/Disable Telephone Alaram...
In the Field Display Setup you can adjust the position of the selected channel in the Present Value Display, Data Log Display, Jumbo Display as well as the Status/Alarm fax. When a channel is not to be represented in the corresponding display then position "0" must be selected for this field.
complete data set will be written to the data log every 3 minutes. The recommended interval is 6 hours. Reference Time: The memory cycle is synchronized using this value. Data Log Interval in Alarm Condition: In alarm condition substantially more data needs to be stored in the log file.
Page 99
alarms will be deactivated during the helium refill. These alarm parameters are set in the Sensor Channels section under the Monitoring System settings (see also "Sensor Chan- nels" on page 96). In the He Measurement Check section you can enable a test that monitors if the same He- level value has been received for more than a monitor period of x days.
HLMU, instead of the BMPC/2 Control Unit, for monitoring. Before you can use the HLMU to measure the helium level, you have to connect the HLMU to one of the Ethernet ports of the BMPC/2 PC, and setup the Windows network settings for this port.
For details on how to setup and check the settings of the HLMU refer to the HLMU man- ual. To use the measurements from the HLMU, you must enable "Monitoring of H2/N2 Level with HLMU" in the BMPC/2 Options window. Z31823_00_08...
Figure 12.23: Helium/Nitrogen Measurement with the HLMU In the setup category LIMIT VALUES (see chapter "Limit Values") you will find among others the following two entries used to setup the limit values for use with the HLMU: - Helium Level (HLMU) - Nitrogen Level (HLMU) It is recommended to use the given default parameters (Normal = 70, Warning = 60, Alarm = 50).
12.3.3.6 BMU 4.x The Bruker Magnet Monitor Unit BMU4 is used on ultra-high field magnets which are not operated in conjunction with an AVANCE NMR console. The BMU4 is then used to mon- itor the liquid helium level in the cryostat, the status (on/off) of the compressor(s) for the active refrigeration system, as well as the temperature of the cooling water for the com- pressor(s).
12.3.3.7 PTC Compressor Bruker’s Aeon NMR magnet systems rely on pulse tube coolers to provide active refrig- eration. The pulse tube cooler in an Aeon magnet is supplied with pressurized helium by a compressor, whose correct operation is constantly monitored by the BMPC. The com- pressor is connected to the industrial PC via an RS232 interface.
If the compressor status (on/off) is monitored through the compressor’s serial interface, the parameter "Compressor Status Timeout” denotes the value from which a counter runs down when the compressor is off. Alarm- and warning values can then be set on this counter to ensure that alarms and warning are issued after the compressor has been off for a certain amount of time.
Page 107
Dialing Parameters / Dialing Rules fields: • Dial Mode: Tone (default) or Pulse • Outside Line Code. This may be required if the BMPC/2 is connected to, for exam- ple, a PABX telephone system. • The international access code.
12.3.4.2 E-mail Setup The parameters for the e-mail settings can be supplied by the local system administra- tor. In some cases it may not be necessary to use a user name and password, whereas the fields will remain blank. Figure 12.27: Tools - Options - E-Mail Setup Z31823_00_08...
12.3.4.3 Contact List (alarm) In this window you can make changes to the contact list used for alarms. Press the cor- responding button in order to add, edit, delete records or to scroll through the list. Figure 12.28: Tools - Options - Contact List (alarm) Through use of the Voice Call and Fax radio buttons, you can determine whether the Voice Call or Fax contact list is displayed.
Default is zero minutes. 12.3.4.5 Voice Box The voice box editor is used to setup the voice box system. This system is pre-config- ured by Bruker service and does not need to be modified. Figure 12.31: Voice Box Configuration Editor Z31823_00_08...
Figure 12.32: Tools - Options - Fax ID • Name: Enter a meaningful name, such as your company and device name. This information will appear in the status line of the fax. • Phone: Enter the number used to reach the BMPC/2. Z31823_00_08...
12.3.4.8 Fax - Fax Header - System Data This window is used to enter all the data concerning the magnet system and BMPC/2. Figure 12.33: Tools - Options - Fax Header: System Data • Magnet Type: The magnet frequency and design.
In this window the data for your company, including the name and contact information of the individuals responsible for the system must be entered. This information is used to contact your company, if necessary, when Bruker receives an alarm fax. Figure 12.34: Tools - Options - Fax Header: Customer Data...
12.3.4.10 Fax - Fax Header - Bruker Office In this window the data for your local Bruker office and the name of the service engineer that installed the system are maintained. Figure 12.35: Tools - Options - Fax Header: Bruker Office...
Figure 12.36: Tools - Options - Fax Voice Box Log When you check the Show Voice Box Log check box, the Voice Box Log window will be displayed as long as you remain in this window. 12.3.5 Service The service area is only accessible by Bruker service personnel. Z31823_00_08...
13 Maintenance and Cleaning 13.1 Maintenance Work To prolong the life of the BMPC/2, Bruker recommends that the maintenance work in this chapter be carried out on a regular basis. 13.1.1 Exchanging the Internal UPS Battery The batteries for the internal UPS (Uninterruptable Power Supply) have a limited life- time.
14 Maintenance and Troubleshooting 14.1 Information Window Messages When an error occurs an error message is displayed inside the information (Info) win- dow and must be acknowledged by the user. These error messages typically need intervention by the user. For example, the error message "Warning possible fan failure pump cabinet"...
If not, check the motor protection switch QM1. To do this open the upper rear panel of the BMPC/2, QM1 is located on the upper left side of the BMPC/2 line control unit. Press the black QM1 button and check if the pump now works.
Page 121
If the valve does not work, check the fuse Q4. To do this open the upper rear panel of the BMPC/2, the Q4 fuse is located on the upper left side of the BMPC/2 line con- trol unit. The black Q4 switch must be in the up position.
Page 122
It was not possible to read the limit data for the temperature T1 from the EEProm, thus supervision of the temperature T1 is not possible. Solution: Reload the values from the backup database to the BMPC/2 as shown for Limit Data P1 fail.
Page 123
It was not possible to read the calibration values for the calculation of the magnet tem- perature T2 from the EEProm, thus calculation and supervision of the temperature T2 is not possible. Solution: A software reset of the BMPC/2 Control Unit usually helps (see also "Control Unit" on page 95).
Page 124
NOTICE Power Supply Failure Even though the BMPC/2 works with a faulty power supply, it is strongly recom- mended that you replace the fuse and/or the power supply as soon as possible. If the second redundant power supply also fails you can no longer control the BMPC/2.
Page 125
Check the function of the Helev transfer program. This program transfers the helium level information and some other data once a day from the BSMS to the BMPC/2. This program must be running in order for the BMPC/2 to receive the newest data.
Page 126
The status interface between the BMPC/2 and the UPS is not connected. Therefore the BMPC/2 will not receive any information about the UPS status. In the event of a longer power failure no alarm procedure will be activated when the UPS battery fails. Addition- ally it is not possible to enable the console output.
130. 14.2 Messages in the Event Log Any messages that appear during operation of the BMPC/2 are displayed In the Event Log of the "Present Values/Events" window. In addition the messages are stored in the Event Log file. There are several different kinds of messages, which can be displayed or hidden using the filter adjustment of the event log browser: •...
130. When this does not correct the error, contact Bruker service. 14.3 Error Message at the Start of BMPC/2 Control Program The following error messages may occur at the start of the BMPC/2 control program: • Database Update Error •...
When a COM Port error occurs, it means that the communications port used for commu- nication with the BMPC/2 cannot be used. Either the port is in use from another program (e.g. SBS terminal or the BMPC/2 Setup Tool), or the cable connection to the control unit is not functioning correctly.
If this is not successful, try to turn the control unit on and off by opening and closing the Q10 safety fuse on the BMPC/2. This is accessible by opening the rear side, upper cover of the BMPC. The Q10 safety fuse is on the upper left-hand side.
Bruker but may have been changed by the customer. Click the Monitor Only button to set the BMPC/2 to the Monitor Only Mode (in the Monitor Only Mode the system status is monitored but no alarms are issued).
WARNING Pump surface can cause serious burns! The surface of the pumps can be extremely hot! Contact with this surface can result in a serious burn. Allow the defective pump to cool down. Avoid touching the operational pump (use the pump tray to pull out the defective pump).
Only use pump oil specifically approved by Bruker for the respective BMPC and Bruker magnet type. The pumps for the standard BMPC/2 (MC5300) need specifically approved oil Do not use the oil used at the Double-Rack BMPC (M147753) or any other oil.
131) to avoid an alarm during the service work. To do so a security code may be needed. This code is defined by Bruker but may have been changed by the customer. Switch the BMPC/2 to the Manual Mode (see "Control panel of the BMPC/2."...
Page 135
Only use pump oil specifically approved by Bruker for the respective BMPC and Bruker magnet type. The pumps for the Aeon BMPC/2 (M136266) need specifically approved oil. Do not use the oil used at the Double-Rack BMPC (M147753) or any other oil.
131) to avoid an alarm during the service work. To do so a security code may be needed. This code is defined by Bruker but may have been changed by the customer. Switch the BMPC/2 to the Manual Mode (see "Control panel of the BMPC/2."...
onds and switch of the pump to be replaced. Switch off the PTC(s): switch off compressor mains of each PTC. Close the return valve V3. WARNING Pump mains cable can be under hazardous voltage! The Double Rack BMPC is equipped with three-phase pumps. The power cable of the three-phase pumps is wired directly to the pumps.
Page 138
Pump 1 and 2 are located in the pump cabinet of the main and extension rack, respec- tively. The motor protection switches QM1 and QM2 are located at the back panel of the extension rack. De-energize the defective pump (pump to be replaced) by switching of the respec- tive motor protection switch QM1 or QM2, respectively (see Figure 5.5: and take...
BMPC and Bruker magnet type. The pumps for the Double-Rack BMPC (M147753) need specifically approved oil. Do not use the oil used at the standard BMPC/2 (MC5300) or the Aeon BMPC/2 (M136266) or any other oil. Contact your Bruker service representative to obtain advice on suitable products.
This chapter is applicable only if the BMPC II is operated with an NMR spectrometer. The voltage supply for the NMR console supplies power to the BMPC/2. The NMR con- sole is attached to terminal X3 of the BMPC/2 line control unit (see "Line Control Unit"...
14.6.1 Adjusting the NMR Console Turn-off Time The adjustment of the turn-off time is made through the KM3 relay. To access the relay open the upper back cover, the KM3 relay is found almost exactly in the middle of the line control unit.
The S4 switch is used to turn on the NMR console. Figure 14.11: Restarting the NMR Console Using the S4 Switch 14.8 Exchanging Fuses Several fuses are used within the BMPC/2. The following sections contain detailed instructions on how to change these fuses. Z31823_00_08...
Cartridge fuse 5 x 20 mm 0.1 A time lag. The Bruker part number is 2241. To replace a fuse open the upper back cover of the BMPC/2. The fuse for the fans are located on the upper right side, marked as FU5, FU6 and FU7.
The BMPC/2 control unit utilizes two safety fuses. The following fuse type is required for the control unit: Cartridge fuse 5 x 20 mm 0.8 A time lag. The Bruker part number is 2250. To exchange a fuse in the control unit: Remove the upper rear cover.
15 Dismantling and Disposal After the lifespan of the instrument, Bruker takes responsibility for disassembly and dis- posal in accordance with the European directive 2012/19/EC WEEE. Bruker BioSpin GmbH offers to take back the components free of charge after usage at the customer site upon request by the customer.
WEEE FR311020911 NMR Hotlines Contact our NMR service centers. Bruker BioSpin NMR provide dedicated hotlines and service centers, so that our special- ists can respond as quickly as possible to all your service requests, applications ques- tions, software or technical needs.
Appendix A Warning Signs Warning High voltage present inside the UPS ..............117 Pump surface can cause serious burns! ........132, 135, 137, 138 Caution Never use pump 1 when valve 2 is open, or pump 2 when valve 1 is open ..43 Heater and APD Settings ..................
Figure 5.11: Industrial PC Rear Panel ............... 31 Figure 5.12: UPS - Uninterruptible Power Supply (P/N 1802515) ......31 Figure 5.13: The UPS Circuit Breaker Used to Switch Off the BMPC/2..... 32 Figure 5.14: Line Control Unit Connector X3 / X4 / X5 ..........33 Figure 5.15: Picture of Connector X6 .................
Need help?
Do you have a question about the BMPC/2 and is the answer not in the manual?
Questions and answers