4. Lead the cable inside the cabinet. Seal the cable entry and ground the shield. See
degree grounding of the power cable and sealing the cable entry (page
5. Attach the cable to a supports with a strain strain relief clamp (a) included in the delivery.
6. Connect the DC+ and DC- conductors to DC terminals with cable lugs (b). Use the bolts,
nuts and washers included in the delivery. Tighten to 70 N·m.
7. Twist the cable shields into bundles and connect them with the cable lugs to the protective
grounding busbars [PE] of the cabinet (c). Tighten to 42 N·m.
8. Install the bars and shrouding removed earlier and close the door.
b
1DC+
1DC-
2DC+
Electrical installation 31
360
32).
2DC-
c
a
11