FYREYE MKII ADDRESSABLE SOUNDER CONTROL MODULE WITH ISOLATOR - INSTALLATION GUIDE
FYREYE MKII ADDRESSABLE SOUNDER CONTROL MODULE WITH ISOLATOR
General
The Fyreye MkII Addressable Sounder Control Module is supplied with a backbox for
surface mounting.
NOTE: The Sounder Control Module is designed for indoor use only.
This module is NOT LOOP POWERED, an adequate 24Vdc input is required with the
necessary battery back up. Note the input voltage should provide adequate current to
operate the ZASC-MI in addition to operating the connected alarm load.
Model No: ZASC-MI
Surface Mounting
1.
Mount the backbox as required and install all cables for termination.
2.
Set the address of the unit as shown on page 3.
3.
Terminate all cables.
4.
Gently push the completed assembly towards the back box until the mounting
holes are aligned and secure with the two mounting screws provided. DO NOT
OVERTIGHTEN.
Isolator Module
The Sounder Control Module is fitted with a bi-directional short-circuit isolator and will
be unaffected by loop short-circuits on either loop input or output.
Document No: GLT-234-7-1
Issue No: 012
INSTALLATION GUIDE
Fyreye MkII Addressable Sounder Control Module With Isolator
Page 1
Author: NRP Jones
Date: 10/05/2021

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FYREYE MKII ZASC-MI and is the answer not in the manual?

Questions and answers

Summary of Contents for Zeta FYREYE MKII ZASC-MI

  • Page 1 FYREYE MKII ADDRESSABLE SOUNDER CONTROL MODULE WITH ISOLATOR - INSTALLATION GUIDE FYREYE MKII ADDRESSABLE SOUNDER CONTROL MODULE WITH ISOLATOR INSTALLATION GUIDE General The Fyreye MkII Addressable Sounder Control Module is supplied with a backbox for surface mounting. NOTE: The Sounder Control Module is designed for indoor use only. This module is NOT LOOP POWERED, an adequate 24Vdc input is required with the necessary battery back up.
  • Page 2: Wiring Details

    FYREYE MKII ADDRESSABLE SOUNDER CONTROL MODULE WITH ISOLATOR - INSTALLATION GUIDE Wiring Details All wiring terminals will accept solid or stranded cables up to 2.5mm Typical Connections Document No: GLT-234-7-1 Author: NRP Jones Page 2 Issue No: 012 Date: 10/05/2021...
  • Page 3: Technical Specification

    FYREYE MKII ADDRESSABLE SOUNDER CONTROL MODULE WITH ISOLATOR - INSTALLATION GUIDE Technical Specification Model ZASC-MI Part Number 48-112 Operating Voltage (Loop) 17 – 28V DC Quiescent Current (Loop) 0.6 mA Fault Current (Loop) 0.6 mA Sounder On Current (Loop) 0.8 mA Operating Voltage (Ext.
  • Page 4 FYREYE MKII ADDRESSABLE SOUNDER CONTROL MODULE WITH ISOLATOR - INSTALLATION GUIDE Document No: GLT-234-7-1 Author: NRP Jones Page 4 Issue No: 012 Date: 10/05/2021...
  • Page 5 FYREYE MKII ADDRESSABLE SOUNDER CONTROL MODULE WITH ISOLATOR - INSTALLATION GUIDE Document No: GLT-234-7-1 Author: NRP Jones Page 5 Issue No: 012 Date: 10/05/2021...
  • Page 6 FYREYE MKII ADDRESSABLE SOUNDER CONTROL MODULE WITH ISOLATOR - INSTALLATION GUIDE Alternative Soft Addressing Option Using our hand held MkII programmer (Part No: 48-004), the unit can be addressed electronically. Step 1: Set all addresses to zero 0000000 Step 2: Connect leads to LOOP IN+ and LOOP IN- as shown below Step 3: Follow the procedure as described in the handheld programmer manual.
  • Page 7: Led Indications

    FYREYE MKII ADDRESSABLE SOUNDER CONTROL MODULE WITH ISOLATOR - INSTALLATION GUIDE LED Indications Status LED Indication Alarm Illuminated red when the Sounder Control Module is in alarm Fault Illuminated yellow when the Sounder Control Module is in fault Open Illuminated yellow when the sounder input is in open state Short Illuminated yellow when the sounder input is in short state Polling...
  • Page 8: Fault Finding

    Fire detection and fire alarm systems – Input/Output Devices Fire detection and fire alarm systems – Short Circuit Isolators Zeta Addressable Sounder Control Module with Isolator ZASC-MI Intended for use in fire detection and fire alarm systems in and around buildings...

This manual is also suitable for:

48-112

Table of Contents