Troubleshooting (When Connected To An Addressable Control Panel); Troubleshooting (When Connected To A System 5000 Control Panel) - EMS WZM Manual

Wireless zone monitor
Table of Contents

Advertisement

Troubleshooting
FireCell Sounders are not working.
Check the wiring from the ZIM's 'Input 1' to the Control Panel's associated re output.
The ZIM's 'Input 1' status will re ect the following:
20K = Normal Condition (Sounders OFF)
3K3 = Alarm Condition (Sounders ON)
FireCell Detector's LEDs are not switching o .
Check the wiring from the ZIM's 'Input 2' to the Control Panel's associated re output.
The ZIM's 'Input 2' status will re ect the following:
20K = Normal Condition (FireCell Detector/Call Point LED's OFF)
3K3 = Alarm Condition (FireCell Detector/Call Point LED's (ON)
I am getting a Fault Condition at the Control Panel.
This fault can occur for the following reasons:
A - Faults on the WZM.
B - The ZIM is not logged on to the WZM? Whilst the ZIM is not logged on, the ZIM's default
output state is energised.
C - Check the wiring from the ZIM's 'Output 2' to the Control Panels associated fault input.
Note: If the Panel's 'Fault' input is end of line (EOL) monitored, ensure the manufacturers
speci ed EOL componant is tted. See the Control Panel instructions for more information.
FireCell Detectors/Call Points are not triggering the Control Panel.
Check the wiring from the ZIM's 'Output 1' to the Control Panel's associated re input.
Note: If the Panel's 'Fire' input is end of line (EOL) monitored, ensure the manufacturers
speci ed EOL componant is tted. See the Control Panel instructions for more information.
Troubleshooting
FireCell Sounders are not working.
Check the wiring from the ZIM's CIC cards 'Sounders - L1 L2' connection to the Control Panel's
connected Sounder Circuit.
FireCell Detectors LEDs are not switching o .
Check the wiring from the ZIM's CIC cards 'Zone - L1 L2' connection to the Control Panel's
connected Zone Circuit.
I am getting a Zone Fault Condition at the Control Panel.
This fault can occur for the following reasons:
A - Faults on the WZM. (Only if WZM faults are monitored on the Zone Circuit).
B - The ZIM is not logged on to the WZM? Whilst the ZIM is not logged on, the ZIM's default
output state is energised. (Only if WZM faults are monitored on the Zone Circuit).
C - The fault may also relate to an incorrect or missing Zone Circuit end of line (EOL). Ensure the
manufacturers speci ed EOL Componant is tted. See the Panel's instructions for more info.
I am getting a Sounder Fault Condition at the Control Panel.
This fault can occur for the following reasons:
A - Faults on the WZM. (Only if WZM faults are monitored on the Sounder Circuit).
B - The ZIM is not logged on to the WZM? Whilst the ZIM is not logged on, the ZIM's default
output state is energised. (Only if WZM faults are monitored on the Sounder Circuit).
C - The fault may also relate to incorrect or missing Sounder Circuit end of line (EOL). Ensure
the manufacturers speci ed EOL componant is tted. See the Panels instructions for more info.
www.acornfiresecurity.com
(when connected to an Addressable Control Panel)
(when connected to a Conventional Control Panel)
www.acornfiresecurity.com