Ziton I/O Unit Installation Guide
General
The Ziton input / output (I/O) unit is available under the
following part numbers:
PART NO
VARIANT TYPE
ZR451-3
Ziton wireless single I/O unit
ZR452-3
Ziton wireless dual I/O unit
The address of the unit is set when programming the
device to the Ziton loop interface (see programming
manual for details). The installation must conform to
BS5839:Part 1 (or applicable local codes). The Ziton I/O
unit is suitable for indoor use only.
Installation of Ziton I/O unit
Ensure that all Ziton I/O units are sited in accordance
with the survey and design details.
Remove the four front plate retaining screws. Retain
these for re-assembly when installation is complete.
Remove the front plate.
Drill required cable entry points for input and output
connections. Recommended cable entry points are
shown in Figure 1.
Position the Ziton I/O unit in the required location and
mark the four xing positions. These are shown in Figure
1.
Using suitable screws and xings attach the device
securely to the wall.
To ensure correct operation, connect the power jumper
across the PIN header on the PCB. The location of header
is shown in Figure 1.
The Ziton IO unit is powered by 6 x AA alkaline batteries.
These are supplied
tted. Should batteries require
replacement, only use speci ed batteries whilst
observing correct polarity as shown in Figure 1.
Fixing
Fixing
Position 1
Position 2
LOGON
ANTENNA
KEEP CABLES AWAY FROM THIS AREA
SERIAL NO
Power
Jumper
0
1
1
2
4
8
16
32
64
CLOSED
F-SAFE
LED
ENABLE
FAULT
INPUT 1 INPUT 2
EXPAN1
EXPAN2
OUTPUT 1
OUTPUT 2
IP- IP+ IP- IP+
3VDC SET RST
3VDC SET RST
N/O COM N/C
N/O COM N/C
Cable
Cable
Entry Points
Entry Points
Fixing
Fixing
Position 3
Position 4
Figure 1
Batteries that have been removed must be disposed of in
accordance with your country's relevant Waste Electrical
and Electronic Equipment (W.E.E.E) regulations.
Please see commissioning manual for log on procedure
details.
Indication LED operation
The Ziton I/O unit has six indication LEDs. Illumination of
these is enabled by pressing the LED enable button
(shown in Figure 2). If the enable button is pressed, the
following LEDs will be illuminated for a time period of 10
minutes and then automatically time out.
Output LEDs:-
Each relay output has a red LED associated with it. If the
output is activated (output bit set to 1) the LED will
illuminate.