INSTALLATION MANUAL Power Alert AquaLink ® ® Controller WARNING FOR YOUR SAFETY - This product must be installed and serviced by a licensed electrician in accordance with AS/NZ 3000 - 2007 and any other local regulations. Before installing this product, read and follow all warning notices and instructions that accompany this product.
Page 2
Page 2 AquaLink Controller | Installation Manual ® ® EQUIPMENT INFORMATION RECORD DATE OF INSTALLATION INSTALLER INFORMATION INITIAL PRESSURE GAUGE READING (WITh CLEAN FILTER) PUMP MODEL hORSEPOWER FILTER MODEL CONTROL PANEL MODEL SERIAL NUMBER NOTES:...
Testing ........12 Basic Navigation............12 Set the System Type ...........12 Set the Clock ...............12 Define Equipment ON/OFF Schedules ....... 13 Test the AquaLink TRI ..........13 Section 7. Install Settings ....... 14 Freeze Protect .............15 Units ................16 Languages..............16 Clear Memory ..............16 Pump ................16...
Page 4 AquaLink Controller | Installation Manual ® ® Section 1. Important Safety Instructions READ AND FOLLOW ALL INSTRUCTIONS All electrical work must be performed by a licensed electrician and conform to all national, state, and local codes. When installing and using this electrical equipment, basic safety precautions should always be followed, including the following: DANGER To reduce the risk of severe injury or death, do not remove the suction fittings of your spa or hot tub.
Page 5
3.5 m of the pool/spa. CAUTION Power to the Aqualink TRI should be supplied by an isolating transformer or through a residual current device (RCD) with a rated residual operating current not exceeding 30mA. Attention Installer: Install to provide drainage of compartment for electrical components.
Controller | Installation Manual ® ® Section 2. System Overview Package Contents Package contents will vary depending on which AquaLink TRI configuration you are installing. AquaLink TRI PSi AquaLink TRI PS • Four Function Controller with removeable • Four Function Controller with removeable...
Before you begin installation, make sure you have the check position before drilling to ensure accuracy. necessary tools and a suitable location to install the AquaLink TRI. NOTE Make sure to mark out the four (4) holes as accurately as possible.
Potentially high voltages in the AquaLink TRI controller can create dangerous electrical hazards, possibly causing death, serious injury or property Anchors (4) damage. Turn off power at the main circuit feeding the AquaLink TRI controller to disconnect the power Mounting center from the system. Bracket WARNING...
Page 9
FILTER AQUALINK TRI AUX 3 PUMP USER INTERFACE GROUND BAR Input Power: Solar Temp Sensor 240 VAC, Ground wire for main Water Temp Sensor 1.67A, Air Temp Sensor 50 Hz iAQUALINK™ J-BOX Figure 2. AquaLink TRI Controller Electrical Wiring Diagram...
Page 10 AquaLink Controller | Installation Manual ® ® Ground Fault Circuit Interrupter Wire the Temperature Sensors Wire the temperature sensors on the 10-pin green WARNING connector (see Figure 2. Wiring Diagram). The air When using electrical products, basic precautions temperature sensor is factory-installed on the 10-pin should always be followed, including the following: green connector (pins 7,8).
(if applicable) 2-Red wire to the (+V) ‘POS’ terminal on the TRi You may wire up to three JVAs on the AquaLink TRI. 3-Yellow/White (B) wire to ‘B’ terminal on TRi Two (2) JVAs are included in PSi and PS (Pool/Spa 4-Black wire (A) to ‘A’...
Programming and Testing MAIN > SETTINGS > SYSTEM TYPE MENU All system programming and installation setup is NOTE This option is only available on AquaLink TRI performed through the AquaLink TRI user interface UI PS and PSi configurations. (even when connected to iAquaLink which only allows Define the system type (Pool/Spa or Pool only) through for basic programming and functionality).
Page 13 AquaLink Controller | Installation Manual ® ® Test the AquaLink TRI Define Equipment ON/OFF Schedules Perform a basic installation test to make sure the MAIN > SETTINGS > SCHEDULES controller turns on the filter pump, the pool heater, Define automatic ON and OFF times for equipment.
• Units Change units of measurement displayed on the User Interface (temperature and time format). Pool Heat Devices Zodiac POOL HEAT Enabled 12:40PM Enabled • Language Filter Pump Change language displayed on the User Interface.
5 seconds. Set outside temperature at which freeze protect function is activated. Activation temperature can be adjusted between 2°C and 5°C Default freeze protection Zodiac INSTALL SETTINGS 12:40PM activation temperature is 3ºC. The freeze protected Freeze Protect >...
Clear all stored values (e.g., auxiliary labels, programs, time format (12-hour AM/PM or 24-hour clock). remote settings, and thermostat settings) from the AquaLink TRI memory. All settings will be reset to CLEAR MEMORY INSTALL SETTINGS default factory settings. Time and date is not cleared.
Backwash Waterfalls Waterfalls Backwash Waterfalls Backwash Chlorinator Whirlpool Whirlpool Chlorinator Whirlpool all Jandy and/or Zodiac lights use the same setting. Chlorinator More More More More More More More More Select Light Type: • Choose from labels listed A-Z on each screen.
Valve Actuators (JVAs) to be assigned SYSTEM SETUP TEMPERATURE ® SYSTEM SETUP TEMPERATURE CALIBRATE CALIBRATE to any auxiliary on the AquaLink TRI controller, so Label Aux > Label Aux > that when you select this auxiliary, the valve turns. Water: 26°C Water: 26°C Temp Calibrate >...
View status of devices connected to the RS-485 More More controller. Depending on your equipment configuration, any combination of the following equipment may be displayed: • FFC - AquaLink TRI Controller • iAL - iAquaLink • SWC - Salt Water Chlorinator • VSP - Variable Speed Pump...
Auto by service technician. • Timeout Indicates that all equipment will remain turned off for three (3) hours and then resume running according to system programming after that time period. Zodiac SERVICE MENU Zodiac SERVICE MENU 12:40PM 12:40PM Pool Mode Auto...
Page 21 Page 21 AquaLink Controller | Installation Manual AquaLink Controller | Installation Manual ® ® ® ® Section 9. Pool/Spa System Menu Flow Diagrams Main Menu MAIN MENU/STATUS Pool Mode OFF/ON Pool Heat Enabled Pool Heater OFF/ON Set to: 28°C Spa Mode OFF/ON Spa Heat Enabled Spa Heater OFF/ON...
® ® ® Install Settings Menu MAIN MENU/STATUS INSTALL SETTINGS VSP Model From Settings, press Temp: °C Jandy/Zodiac both Up/Down Arrow Set Temp Intelliflo VS buttons for 5 seconds Freeze Protect Pool Mode OFF/ON Filter Pump to display Install Settings Equipment Speeds <RPM>...
Page 23 Page 23 AquaLink Controller | Installation Manual AquaLink ® ® Controller | Installation Manual ® ® Section 10. Pool Only System Menu Flow Diagrams 10.1 Main Menu MAIN MENU/STATUS Pool Mode OFF/ON Pool Heat Enabled Temp 1 OFF/ON Set to: 28°C Pool Heat Enabled Temp 2 OFF/ON...
® ® 10.2 Install Settings Menu MAIN MENU/STATUS INSTALL SETTINGS VSP Model From Settings, press Temp: °C Jandy/Zodiac both Up/Down Arrow Set Temp Intelliflo VS buttons for 5 seconds Freeze Protect Pool Mode OFF/ON Filter Pump to display Install Settings Equipment Speeds <RPM>...
Page 25 Page 25 AquaLink Controller | Installation Manual AquaLink Controller | Installation Manual ® ® ® ® Section 11. Glossaries Cleaner Lockout The pool cleaner will only activate if the system is in 11.1 Glossary of Safety Delays and pool mode and water is circulating.
Page 26
This message is displayed during pool/spa switching. been detected by the freeze protection sensor, and that The AquaLink TRI waits 35 seconds while the valves equipment assigned to freeze protection are active (for turn from pool position to spa position (or vice-versa) example, the filter pump).