Geostar ASTON Series Installation Manual page 29

Heating | cooling | hot water
Hide thumbs Also See for ASTON Series:
Table of Contents

Advertisement

Wiring Schematics cont.
Dual Capacity Split - 208-230/60/1 cont.
Aurora LED Flash Codes
Slow Flash
1 second on and 1 second off
Fast Flash
100 milliseconds on and 100 milliseconds off
Flash Code
100 milliseconds on and 400 milliseconds off with a 2 second pause before repeating
Random Start Delay (Alternating Colors)
Configuration LED (LED2, Yellow)
Status LED (LED1, Green)
Fast Flash
No Software Overide
Configuration LED (LED2, Yellow)
Fast Flash
DIP Switch Overide
Fault LED (LED3, Red)
Fast Flash
Fault LED (LED1, Red)
Status LED (LED3, Green)
Normal Mode
OFF
Normal Mode
Input Fault Lockout
Flash Code 1
Control is Non-Functional
High Pressure Lockout
Flash Code 2
Test Mode
Low Pressure Lockout
Flash Code 3
Lockout Active
Future Use
Flash Code 4
Dehumidification Mode
Freeze Detection – FP1
Flash Code 5
Future Use
Reserved
Flash Code 6
Future Use
Condensate Overflow Lockout
Flash Code 7
Load Shed
Over/Under Voltage Shutdown
Flash Code 8
ESD
Future Use
Flash Code 9
Future Use
Future Use
Flash Code 10
FP1 and FP2 Sensor Error
FP1 Sensor Error
Flash Code 11
Aurora Timing Events
Normal Mode
Event
Random Start Delay
5 to 80 seconds
Compressor On Delay
5 seconds
Compressor Minimum On Time
2 minutes
Compressor Short Cycle Delay
4 minutes
Blower Off Delay
30 seconds
Fault Recognition Delay – High Pressure
Less than 1 second
Start-Up Bypass – Low Pressure
2 minutes
Fault Recognition Delay – Low Pressure
30 seconds
Start-Up Bypass – Low Water Coil Limit
2 minutes
Fault Recognition Delay – Low Water Coil Limit
30 seconds
Fault Recognition Delay – Condensate Overflow
30 seconds
Thermostat Call Recognition Time
2 seconds
Water Valve Slow Open Delay
90 seconds
ABC SW2 Accessory Relay
DESCRIPTION
SW2-4
SW2-5
Cycle with Blower
ON
ON
Cycle with Compressor
OFF
OFF
Water Valve Slow Opening
ON
OFF
Cycle with Comm. T-stat Hum Cmd
OFF
ON
LED1
FP1 – 15
HP
ECM PWM
P4
R
FP2 – 15
HP
P13
LP
Fault
LP
ACC – Dip 4
FP2
ACC – Dip 5
FP2
LED3
CC – Dual/Single
FP1
SW1 Test
G
FP1
L – Pulse/Continuous
REV
Status
Reheat/Normal
REV
RV – K1
CC2
AURORA BASE
CC – K2
CONTROL™
G
P5
CC Hi – K3
LO
HI
CCG
CC
Fan – K4
FG
F
P11
R
Alarm – K5
JW2 - Alarm
F
Acc – K6
CC
P9
Factory Fan Connection
G
Y1
Field Connections
Field Connections
P2
P1
ASTON & ASTON ADVANCED DUAL-CAPACITY OUTDOOR SPLIT SERIES INSTALLATION MANUAL
OFF
Slow Flash
ON
OFF
Slow Flash
Fast Flash
Flash Code 2
L1
Flash Code 3
Flash Code 4
Flash Code 5
Flash Code 6
Flash Code 7
CC -
Compressor Contactor
CO -
Condensate overflow sensor
K5 -
DHW pump relay
Test Mode
Loop pump relay
K6 -
1 second
PSC Fan Speed Relay
CR3 -
< 1 second
CR4 -
PSC Fan Power Relay
5 seconds
CS -
Compressor Solenoid
15 seconds
F1 and F2 -
Fuses
2 seconds
FP1 -
Freeze protection sensor
Less than 1 second
HP -
High pressure switch
FP -
Freeze protection switch
30 seconds
LP -
Low pressure switch
30 seconds
30 seconds
30 seconds
30 seconds
2 seconds
90 seconds
On
Off
LED2
1
o
F/30
o
F
EH1
2
Y
o
F/30
o
F
RV – B/O
3
Config
P3
EH2
4
C
5
EH1
C
6
CO
7
N/A
8
SW2
(+)
P6
(-)
R
C
(+)
P7
LED5
(-)
G
Com1
R
C
P8
LED4
G
Com2
R
R
97P840-24
4/3/13
Legend
Factory Low voltage wiring
Thermistor
T
Factory Line voltage wiring
Field low voltage wiring
Light emitting diode - Green
G
Field line voltage wiring
Optional block
Relay coil
DC Voltage PCB traces
Junction
Capacitor w/ bleed resistor
Quick connect terminal
Switch - Condensate overflow
Wire nut
Switch - High pressure
Field wire lug
Switch - Low pressure
Ground
Relay Contacts-
2
3
1
Polarized connector
N.O., N.C.
P
Fuse
Current Transducer (CT)
Breaker
PB1, PB2 -
Power blocks
PS -
Power strip
RV -
Reversing Valve coil
SW1 -
DIP package 5 position AXB
SW1 -
TEST MODE ABC Board
SW2 -
DIP package 8 position ABC Board
RP -
Relay – Loop Pump
TS -
Thermal limit switch
HWL -
Hot water limit sensor
SC -
Start Contactor
SR -
Start Relay
WCL -
Water Coil Limit Sensor
Notes
1 – Flow Center may be either factory or field installed.
2 – Field installed SPST relay required for duel fuel applications.
Duel Fuel Wiring Diagram
Thermostat
Using Field Installed Relay
Y1
1st Stage Compressor
Y2
2nd Stage Compressor
O
Reversing Valve
Fossil Fuel
L
Fault Signal
Furnace
C
C
Common
Common
R
R
24 VAC
24 VAC
W
Auxiliary Heat Relay
G
G
Fan
Auxiliary
Heat Relay
W
Auxiliary Heat Relay
Note 2: Field installed SPST dual fuel relay
(Required for dual fuel installation)
29
Split
Y1
Y2
O
P1
LO
C
R
P2
ES
= chassis

Advertisement

Table of Contents
loading

Related Products for Geostar ASTON Series

This manual is also suitable for:

Aston advanced series

Table of Contents