Disposal; Technical Data - Helios AirPal 1750 H Installation And Operating Instructions Manual

Table of Contents

Advertisement

Available languages

Available languages

Installation and Operating Instructions
EN
m
DANGER
CHAPTER 2

TECHNICAL DATA

Air purifier AirPal 1750/2200 H
m
Risk of personal injury and equipment damage!
The packages may have an eccentric centre of gravity. If the packages are lifted incorrectly, they can be dropped. Falling or
overturned packages may cause serious injury.
1�10 Disposal
Dispose of all components and filters in an environmentally-friendly manner in accordance with the local codes, prac-
tices and guidelines. An authorised specialist waste processing company must dispose of the unit or the individual
components.
The appointed contractor must ensure that the components are separated according to material types.
The technical specifications of both units AirPal 1750 H/2200 H are shown below. The units (filter assembly, closing
doors, distances, etc.) must installed correctly to obtain maximum efficiency from the device. The device's sound level
and electrical performance may vary depending on the ambient and operating conditions (temperature, humidity).
Vmin (m³h)
Vmax (m³h)
Max. Served Area* (m²)
LwA (min) (dB(A))
LwA (max) (dB(A))
LpA (min) @1m (dB(A))
LpA (max) @1m (dB(A))
Power Cons. MAX (W)
Voltage (V)
Current (A)
Frequency (Hz)
Height (mm)
Width (mm)
Depth (mm)
Weight (kg)
Protection (IP)
Filter 1
Filter 2
Filter 3
Flow rate control
*with 4 air changes per hour and 3 m room height
AirPal 1750 H
AirPal 2200 H
300
370
1750
2200
146
183
30
31
65
68
22
23
57
60
494
473
230
230
2.2
2.1
50
50
2313
2332
717
717
566
720
150
185
20
ePM10 70%
ePM1 80%
HEPA H14
Variable