Installation
1.
Disconnect your smartphone/tablet or computer from the device WiFi. Open your smartphone or tablet WiFi
settings.
To open WiFi Settings on smartphones or tablets:
Go to Settings>WiFi or Settings>Connections>WiFi.
To open WiFi Settings on computers: Click on the
WiFi icon [
or
] in the desktop system tray.
2. Either select the homeowner' s WiFi network or Forget the PPSxxxxx network.
3. The Connection LED on the device will change to Blinking Green once connected to the homeowner' s WiFi network
and then turn to Solid Green when connected to the internet.
Note: If the Communication LED is Red, verify that the homeowner' s WiFi network is working properly.
Note: If the Communication LED stays Blinking Green, verify that the device is setup on the Link2O app or www.
mylink2o.com.

Parameter List

Parameter
Upper Pressure Setting (UPS)
Lower Pressure Setting (LPS)
Over Pressure
Service Factor Amps
Extended Run Time
Dry Run
Dry Run Delay
Dry Run Detection Time
Pressure
Rfssi?
Connect Pentek CSC to Home WiFi
Unit of Measure
Default
psi
50
psi
30
psi
80
A
-
Minutes
60
-
Enabled
Minutes
Seconds
30
psi
-
Value
Min.
Max.
Sets the pressure for when the pump stops
10
90
running. Traditionally the Cut-Out setting.
Sets the pressure for when the pump starts
0
UPS - 1
running. Traditionally the Cut-In setting.
UPS + 5
100
Service factor amps (max. load) of motor the
0
12
Number of minutes device can run before it
1
65000
Disabled
Enabled
Enables or disables Dry Run Detection
Time device waits to restart pump when Dry
1
65000
Time the device takes to recognize Dry Run
1
65000
0
100
Displays the actual system pressure at
Description
Sets Over Pressure Fault value.
device is operating.
faults on Extended Runtime
Run is detected.
condition.
6