Refer to Table 3.4 content for one key to clear EEPROM operation, after cleared, the product will automatically turn to the
indoor unit ·outdoor unit handshaking stage, RUN light is constantly on, until RUN light turns to flash the product will enter
normal control stage and control the indoor unit.
NO.
1
Prompt
●You can also clear EEPROM through Mapping Table control, refer to 4.8 for specific content of clearing EEPROM.

3.1.6 Remote Server IP Address Setting

Refer to the login interface in Figure 3.3 and enter, click <Network Setting> and enter IP setting interface. <Remote Server
IP> will be displayed, this IP address is the IP address when considered Modbus as client, computer for management and host
computer as server, based on above operation, please set this IP address with the same IP address as computer for management
and host computer, at the same time <Remote Server Port> is the monitoring port of computer for management and host
computer, default as 502, range: 0~65535.
You can also spot check and set remote server IP address and port number through key + digital tube. Press and hold
SW6+SW7 key for 3s and enter the setting mode, as shown in below Table 3.5.
NO.
1
2
Table 3.4 Clear EEPROM with key
·Power on and there's no content displayed on the digital tube, press the Select key
(SW7).
·Press and hold until the digital tube displays "EEcL." and disappear after 1s to
reset factory configuration, but please not it's valid within 60s after powered on.
Table 3.5 Set the remote server IP address and port number with key
·Press Up (SW5) or Down (SW8) until it displays "Si.".
·In "Si." Menu, press Select key (SW7) to confirm to enter remote server IP setting
mode.
·After set, please press Eject/Switch key (SW6) to exit.
·Press SW7 so that the IP number becomes editable, flashing in 1Hz.
·In menu, press Select key (SW7) so that default IP flashes and becomes editable.
·Press Eject/Switch key (SW6) to switch the flashing and change editable area.
·Press Up (SW5) or Down (SW8) to change the IP number.
·As above.