Heat pump Aqua HP 9 kW & 12 kW
Item no. 14983109 & 14983112
Installation
The heat pump shall be installed by a qualified professional.
The Pahlén heat pump must be installed outdoors, as it takes its energy from the surrounding air. It must be placed in a well
ventilated area. Do not place anything by the heat pump that can stop the air flow at the air intake or outlet. Behind the heat
pump there has to be a free space of 50 cm or the capacity of the heat pump can be reduced or even disappear. If the air
between the air inlet and the air outlet affect one another the efficiency can be deteriorated.
The frame must be fixed with bolts (M10) in a concrete base or fittings.
Note that when the heat pump is in operation there will be condence water at the bottom of the heat pump. Put in and fix the
drain nozzle in the hole underneath. Connect the pipe to drain the condence water.
Skimmer
Electrical installation
The electrical installation shall be made by a qualified electrician according to the wiring diagram below and shall be preceded
by an earth fault relay. Do not start the heat pump until all cables are connected and the after-check has been completed.
220-240V
1-fas/50Hz
Earthing
14983109
Fuse
16A
Wire
3x2,5 mm²
Note!
The data above is according to a power cable less than 10 m.
If the power cable is more than 10 m the cable diameter must be increased.
Copyright © 2009 Pahlén AB, Box 728, SE-194 27 Upplands Väsby, Sweden
Tel. +46 8 594 110 50, Fax +46 8 590 868 80, e-mail: info@pahlen.se, www.pahlen.com
Main drain
Filter
Pump
Distribution box
(customer prepare)
Fuse
Earth fault relay
14983112
16A
3x2,5 mm²
Inlet
Pahlén Aqua HP
Drain
Power cord
Heat pump
wiring board
Installation instruction
MA20-10E