Download Print this page

Wireless Transmitter Module (869Mhz); Function Test; Programming To Tunstall Equipment; Self-Test And Battery Test - Tunstall 68005/96 User & Installation Instructions

Radio smoke detector

Advertisement

Available languages

Available languages

User/Installation Instructions for Radio Smoke Detector
Model Number: 68005/96

Wireless Transmitter Module (869MHz)

The Smoke Detector is equipped with a wireless 869MHz transmitter
module. This will transmit alarm signals via Tunstall Emergency
equipment to monitoring centres.

Function test

Attention: The smoke detector generates a very
powerful and shrill tone which can be harmful to
your ears. Please keep at least a distance of 50 cm
during the function test.
Perform the function test every month. Proceed as follows:
1. Check if the LED is flashing.
2. Press the fibre-optical button for at least 1 sec.: If a signal tone is
generated, the detector works properly. If no signal tone is
generated, please replace the batteries.
3. If after replacing the batteries a tone can still not be heard then the
smoke detector is damaged and has to be replaced by a new one.

Programming to Tunstall equipment

Register the radio smoke detector to Tunstall emergency equipment
by placing the emergency equipment in trigger registration mode and
pressing the fibre-optical button for at least 1sec. A signal tone is gen-
erated and the detector transmits a radio message to the emergency
equipment. Check that the registration is successful by pressing the
fibre-optical button again to raise an emergency call. If no alarm is giv-
en, please check the following:
-
Battery state?
-
Smoke detector faulty?
-
Emergency equipment within radio range?
-
Emergency equipment programming correctly?

Self-test and battery test

The smoke detector identifies smoke at an early stage of development.
An independent self-test permanently controls the function of the
smoke evaluation. Possible faults are shown per alarm signal
(signal tone or light diode). The power supply is continuously checked
through the battery test. If the battery voltage decreases under a de-
fined point, the smoke detector signals 30 days long that the battery
should be replaced. The smoke detector continues to function fully
during these 30 days, however the battery should be replaced as soon
as possible. Life time of the battery: approx. 10 years (using U9VL-J-
P). Check the functionality of the smoke detector after a battery
change by pressing the fibre-optical-button [item 2 function test] for a
few seconds.
Alarm muting
The alarm muting can be activated by pressing the fibre-optical button.
The smoke detector will mute for approximately 10 minutes and then
reset itself to normal operation.
Serial number to be found on the "type label"
Replace all smoke detectors after 10 years. The recommended ex-
change date is located on the label of the smoke detector!
smoke inlet apertures
fibre-optical button
D6707324A1
Operation- and alarm signals
Signal
Signal tone
LED
No Tone
Flashes each 40 s
Loud
Flashes
interval tone
Short signal tone
Flashes alternating with
each 40 s
signal tone
Short signal tone
Flashes parallel to signal
each 40 s
tone
No Tone
Flashes every 10 s
No Tone
Flashes 3x every 43 s
Maintenance
A maintenance service should be provided every 6 months (or in case
of a failure message) in order to guarantee the operating safety of the
smoke detector over a long period.
To carry out this service please proceed as follows:
- Remove the smoke detector from the base (turn counter clock-
wise) and clear away the dust.
- Wipe the smoke detector with a damp cloth.
- Place the smoke detector back in the base and turn it clockwise
until it is locked.
Note: the smoke detector will not engage inside the base
without the battery inserted.
- Check if the automatic self-test (smoke detector flashes approxi-
mately every 40 seconds) is executed.
- Perform a function test.
Meaning of symbols
The crossed-out refuse container on this product
indicates that it should not be disposed with other
business waste at the end of its working life. To
help ensure that valuable resources are reused
and recycled and to prevent possible harm to the
environment.
Product-Approval according to EN 14604 and
VdS 2344 by the VdS Schadensverhütungs
GmbH.
Technical data
Detection method: .................................................... Tyndall-effect
Operating voltage: .............................................................. 9V DC
Alarm indication: ............................................. optical and acoustic
Class of protection: .............................................. EN 14604:2005
Battery to be used with wireless module: .......... Ultralife U9VL-J-P
Average lifetime of the U9VL-J-P battery @15-20ºC: ....... 10 years
Operating temperature range: .................................... -10 to+60 °C
Max. monitored area: ...................................... 60 m² till 6 m height
Indicator: .......................................................................... red LED
Signal tone: ............................................................. >85 dB(A)/3m
Dimensions without base (Ø x H):...........................100 x 35,0 mm
Dimensions with base (Ø x H): ...............................100 x 51,0 mm
Mounting hole distance on base: ........................... 28,0 - 65,0 mm
Housing material/colour: ................................................ABS/white
Wireless range: ................................................ Typically 25 - 50m
Detector Life: ................................................................... 10 years
VdS Approval: ............................ G 202042 and 0786-CPD-20681
D of C...................uk.tunstall.com/media/resources/literature
CE Approval: .................................................................... marked
Please contact:
Tunstall Healthcare (UK) Ltd
Meaning
Automatic
self-test,
regular operation mode
Local smoke alarm or
function test
Failure / pollution
Indication
for
replacement
Alarm muting
Alarm memory (alarm
in the previous 24 h).
Cleared
by
pressing
fibre-optical button
Whitley Lodge
Whitley Bridge
Yorkshire, DN14 0HR, UK
+44 1977 661234
www.tunstall.co.uk
e-mail: enquiries@tunstall.co.uk
Seite 2 von 4