SPECIFICATIONS

Power Factor specifications for the Total Access PS/BC are listed in
tions are listed in
Table
Power Output
50 watts
150 watts
325 watts
Specification
10
3.

Table 2. Power Factor and Efficiency

Power Output vs. Efficiency
Power Factor
> 98%
> 99%
> 99%

Table 3. PS/BC Specifications

Environmental
Operating Temperature:
Derated Operation,
Linear:
Storage Temperature:
Relative Humidity:
Max Heat Dissipation:
Physical
Height:
Width:
Depth:
Weight:
Electrical
AC Input:
DC Output:
Max power up to 50°C:
Max power @ 70°C:
Power Output:
Compliance
NEBS:
UL:
ETL:
FCC:
Efficiency
> 81%
> 89%
> 91%
Description
–40°C to 50°C
50°C to 70°C (0.05 amp/°C)
–40°C to 85°C
95 percent noncondensing
29 watts at 325 watts output
50 watts maximum during overload
3.45 inches
15.35 inches (with mounting tabs)
2.92 inches
5.5 pounds
120 Volts, 3.75 amps max, 60 Hz
–54 Volts, 6 amps
6 amps
5 amps
325 watts
Level 3+
60950
Listed
Part 15, Class A
Table
2. PS/BC specifica-
Power Dissipation
11 watts
18 watts
29 watts
61180043L2-5D