Haier 1U35YEGFRA Service Manual page 19

Outdoor unit dc inverter
Hide thumbs Also See for 1U35YEGFRA:
Table of Contents

Advertisement

TC( )
Fgh_t1 2
Fgh_t2 2
Fgh_t3 2
Fgh_t4—2
Fgh_t5—2
Normal
N Decreasing at the speed of 1HZ/1 second
P Decreasing at the speed of 1Hz/10 seconds
Q Continue to keep the last-time instruction cycle
R Increasing at the speed of 1Hz/10seconds
Remarks: the outdoor unit
7.1.5.3 The control of preventing the over current of the compressor:
During the starting process of the compressor, if the current of the compressor is greater than 12.5A
for 3 seconds, stop the compressor and alarm, after 3 minutes, start it again, if such state appears 3
times in 20 minutes, stop the compressor and alarm, and confirm the malfunction. Then continue to
run it only after the power is off.
During the starting process of the compressor, if the AC current is greater than 9A, the frequency of
the compressor decreases at the speed of 1HZ/second.
During the starting process of the compressor, if the AC current is greater than 8A, the frequency of
the compressor decreases at the speed of 0.1HZ/second.
During the starting process of the compressor, if the AC current is greater than 7.5A, the frequency
of the compressor increases at the prohibited speed.
During the starting process of the compressor, if the AC current is greater than 6.5A, the frequency
of the compressor increases at the speed of no faster than 0.1HZ/second.
7.1.5.4 The protection function of AC current:
During the starting process of the compressor, if the AC current is greater than 12.5A for 3 seconds,
stop the compressor and alarm, after 3 minutes, start it again, if such state appears 3 times in 20
minutes, stop the compressor and alarm, and confirm the malfunction. Then continue to run it only
after the the power is off.
During the starting process of the compressor, if the AC current is greater than 9A, the frequency of
the compressor decreases at the speed of 1HZ/second.
During the starting process of the compressor, if the AC current is greater than 8A, the frequency of
The compressor stops
N Decreasing the frequency rapidly
P Decreasing the frequency slowly
Q Prohibiting increasing the frequency
R Increasing slowly
19
Functions and control
(09K)
Fgh_t1 63
Fgh_t2 60
Fgh_t3 57
Fgh_t4 52
Fgh_t5 40
Domestic air conditioner