Make certain that all electrical work is carried out by qualified OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY personnel according to the local laws and regulations and this TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE installation manual, using a separate circuit. SPECIFICALLY DESIGNED FOR USE WITH THE Insufficient capacity of the power supply circuit or improper...
In Europe, EN378 provides the necessary guidance for this logbook. RZQ71D3V1B + RZQ100~140D9V1B + RZQ100~140B9W1B Installation manual Split System air conditioners 4PW60930-1...
150 mm of the underside of the unit) or case the user may be required to take adequate use a drain plug kit (option) in order to measures. avoid drainwater dripping. (See figure). Installation manual RZQ71D3V1B + RZQ100~140D9V1B + RZQ100~140B9W1B Split System air conditioners 4PW60930-1...
Pipe Ø of piping material Minimal thickness t (mm) 6.4 / 9.5 / 12.7 0.80 15.9 1.00 19.1 1/2H O=Annealed 1/2H=Half hard Only use annealed material for flare connections. Installation manual RZQ71D3V1B + RZQ100~140D9V1B + RZQ100~140B9W1B Split System air conditioners 4PW60930-1...
Pinch the pipe Outdoor unit Less than a month Pinch or tape the pipe Regardless of the Indoor unit period Great caution is needed when passing copper tubes through walls. RZQ71D3V1B + RZQ100~140D9V1B + RZQ100~140B9W1B Installation manual Split System air conditioners 4PW60930-1...
Make sure to keep the valve open during operation. The names of parts of the stop valve are shown in the figure. Service port stop valve Field piping connection Valve cover Installation manual RZQ71D3V1B + RZQ100~140D9V1B + RZQ100~140B9W1B Split System air conditioners 4PW60930-1...
Page 11
Ø12.7 50~60 N•m 16.2~16.6 R=0.4~0.8 Tightening torque Ø15.9 63~75 N•m 19.3~19.7 Liquid pipe 13.5~16.5 N•m Gas pipe 22.5~27.5 N•m Check for refrigerant leakage after tightening the cap. RZQ71D3V1B + RZQ100~140D9V1B + RZQ100~140B9W1B Installation manual Split System air conditioners 4PW60930-1...
–100.7 kPa. After keeping the system under that condition for more than one hour, check if the vacuum gauge rises or not. If it rises, the system may either contain moisture inside or have leaks. Installation manual RZQ71D3V1B + RZQ100~140D9V1B + RZQ100~140B9W1B Split System air conditioners 4PW60930-1...
– – b (G1+G2) 30=(5+54) 30=29 Ø6.4 R2=0.9 kg For future servicing, mark with a circle the selected amount on the Refrigerant charge amount=R=R1+R2=0.0+0.9=0.9 kg tables below RZQ71D3V1B + RZQ100~140D9V1B + RZQ100~140B9W1B Installation manual Split System air conditioners 4PW60930-1...
Page 14
Make sure that stop valves both on liquid and gas side are open and be sure to operate the unit in cooling operation during test run. Installation manual RZQ71D3V1B + RZQ100~140D9V1B + RZQ100~140B9W1B Split System air conditioners 4PW60930-1...
Follow the electric wiring diagram for electrical wiring works. Form the wires and fix the cover firmly so that the cover may be fit in properly. RZQ71D3V1B + RZQ100~140D9V1B + RZQ100~140B9W1B Installation manual Split System air conditioners 4PW60930-1...
(1) European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16 A and ≤75 A per phase. Installation manual RZQ71D3V1B + RZQ100~140D9V1B + RZQ100~140B9W1B Split System air conditioners 4PW60930-1...
30 minutes. In case of a wireless remote controller, execute the test run only after having installed the indoor unit decoration panel with infra- red receiver first. RZQ71D3V1B + RZQ100~140D9V1B + RZQ100~140B9W1B Installation manual Split System air conditioners 4PW60930-1...
Need help?
Do you have a question about the RZQ71D3V1B and is the answer not in the manual?
Questions and answers