Wiring Specifications - Linear GSLG-A Installation Manual

Slide gate operator
Hide thumbs Also See for GSLG-A:
Table of Contents

Advertisement

Wiring Specifi cations
Refer to the following steps for details on power and
accessory wiring for the operator.
WARNING
ALL AC ELECTRICAL CONNECTIONS TO THE POWER SOURCE AND
THE OPERATOR MUST BE MADE BY A LICENSED ELECTRICIAN
AND MUST OBSERVE ALL NATIONAL AND LOCAL ELECTRICAL
CODES.
USE COPPER WIRE ONLY!
AC Power Wiring
1. Find the listing on this page corresponding to the model, voltage and
horsepower rating of your operator.
2. The distance shown in the table is measured in feet from the
operator to the power source. DO NOT EXCEED THE MAXIMUM
DISTANCE. These calculations have been based on standard 115 V
and 230 V supplies with a 10% drop allowable. If your supply is under
the standard rating, the runs listed may be longer than what your
application will handle, and you should not run wire too near the
maximum distance for the gauge of wire you are using.
3. When large-gauge wire is used, a separate junction box (not
supplied) may be needed for the operator power connection.
4. Wire length calculations are based on the National Electrical Code,
Article 430 and have been carefully determined based on motor
inrush, brake solenoids, and operator requirements.
5. Connect power in accordance with local codes. The green ground
wire must be properly connected.
6. Wire insulation must be suitable to the application.
7. Electrical outlets are supplied in all 115 VAC models for convenience
with occasional use or low power consumption devices only. If
you choose to run dedicated equipment from these devices, it will
decrease the distance for maximum length and the charts will no
longer be accurate.
DC Control and Accessory Wiring
1. All control devices are now 24 VDC, which can be run up to 2000
feet with 14 AWG wire.
2. Control wiring must be run in a separate conduit from power wiring.
Running them together may cause interference and faulty signals in
some accessories.
3. A three-wire shielded conductor cable is required to connect two
operators together for dual operation. You must use Belden 8760
Twisted Pair Shielded Cable (or equivalent) only – P/N 2500-1982,
per foot). See Page 25 for details of this connection. Note: The shield
wire should be connected in both the operators.
GSLG-A Slide Gate Operator Installation Guide
MODEL GSLG-A SINGLE PHASE POWER WIRING
MAXIMUM DISTANCE (FEET)
VOLTS & HP
SINGLE
222
354
115 VOLTS
566
1/2-HP
900
1430
178
282
115 VOLTS
450
3/4-HP
716
1140
160
254
115 VOLTS
406
1-HP
646
1026
760
1200
208 VOLTS
1924
1/2-HP
3060
4864
604
958
208 VOLTS
1526
3/4-HP
2424
3856
544
864
208 VOLTS
1374
1-HP
2184
3476
894
1422
230 VOLTS
2264
1/2-HP
3600
5724
710
1128
230 VOLTS
1796
3/4-HP
2852
4538
640
1016
230 VOLTS
1616
1-HP
2570
4090
MODEL GSLG-A THREE PHASE POWER WIRING
MAXIMUM DISTANCE (FEET)
VOLTS & HP
SINGLE
1142
208 VOLTS
1816
1/2-HP
2890
920
208 VOLTS
1464
3/4-HP
2330
714
208 VOLTS
1136
1-HP
1804
1344
230 VOLTS
2137
1/2-HP
3400
1084
230 VOLTS
1723
3/4-HP
2741
840
230 VOLTS
1336
1-HP
2124
3841
460 VOLTS
6106
1/2-HP
9712
3279
460 VOLTS
5212
3/4-HP
8291
2689
460 VOLTS
4274
1-HP
6798
- 2 -
WIRE GAUGE
DUAL
111
12
177
10
283
8
450
6
715
4
89
12
141
10
255
8
358
6
570
4
80
12
127
10
203
8
323
6
513
4
380
12
600
10
962
8
1830
6
2432
4
302
12
478
10
763
8
1212
6
1928
4
272
12
432
10
686
8
1092
6
1738
4
447
12
711
10
1132
8
1800
6
2862
4
355
12
564
10
898
8
1426
6
2269
4
320
12
508
10
808
8
1285
6
2045
4
WIRE GAUGE
DUAL
571
12
908
10
1445
8
460
12
732
10
1165
8
357
12
568
10
902
8
672
12
1069
10
1700
8
542
12
862
10
1371
8
420
12
668
10
1062
8
1921
12
3053
10
4856
8
1640
12
2606
10
4146
8
1345
12
2437
10
3399
8
P1222 Revision X5 6-22-2011