Download Print this page
Pittway System Sensor WFDT Installation And Maintenance Instructions

Pittway System Sensor WFDT Installation And Maintenance Instructions

Vane-type waterflow detectors

Advertisement

Quick Links

INSTALLATION AND MAINTENANCE INSTRUCTIONS
WFDT/WFDTH Vane-type
Waterflow Detectors
Specifications
Contact Ratings:
Triggering Threshold Bandwidth (Flow Rate):
Static Pressure Rating:
Dimensions, Installed:
Operating Temperature Range:
Shipping Weight:
Enclosure Rating:
The WFDTH can be installed between 2X4 stud wall construction.
Important
Please Read Carefully And Save
This instruction manual contains important information
about the installation and operation of waterflow detectors.
Purchasers who install waterflow detectors for use by
others must leave this manual or a copy of it with the user.
Read all instructions carefully before beginning.
Use vane-type waterflow detectors in wet-pipe systems
only. DO NOT USE IN DRY-PIPE, DELUGE, OR PRE-AC-
TION SYSTEMS. The sudden inrush of water in such sys-
tems may break the vane off or damage the mechanism. Do
not use in potentially explosive atmospheres. Do not leave
unused wires exposed.
Principles Of Operation
Vane-type waterflow detectors mount to water filled pipes
in sprinkler systems. Water flow in the pipe deflects a vane.
Deflection of the vane produces a switched output, usually
after a specified delay.
All WFDTs have a pneumatically controlled mechanical
delay mechanism. Delays are noncumulative; they reset if
the flow of water stops before the entire delay has elapsed.
All detectors will activate on a sustained flow of water
greater than 10 gallons per minute (gpm) but will not
activate if the flow rate is less than 4 gpm.
Compatible Pipe Tees
The WFDT and WFDTH fit 1 " to 1
and brass, 1 " to 2 " sweat brass, 1
and 1 " pvc plastic tees having a 1 " threaded NPT branch
(see Figure 1 and chart for recommended tee depths).
N770-05-00
Technical Manuals Online! - http://www.tech-man.com
Two sets of SPDT (Form C)
10 A @ 125/250 VAC; 2.5 A @ 24 VDC
4 - 10 GPM
250 PSI (Max.)
WFDT–
4
5
/
16
5
WFDTH–
4
/
16
32° F - 120° F (0° C - 49° C)
2.6 lbs.
WFDT–
NEMA Type 4, as tested by Underwriters Laboratories, Inc. (U.L.)
WFDTH–
Indoor use only, as tested by U.L.
CAUTION
" NPT threaded ferrous
1
/
2
" polybutylene plastic
1
/
2
" H × 3
" W × 6
" D
3
/
3
/
4
4
" H × 3
" W × 6
" D
9
3
/
/
16
4
Approximate Tee Depth Requirements
Tee Depth
Threaded Sweat Poly B CPVC
1 × 1 × 1"
1
2
/
8
× 1
× 1"
1
1
1
1
/
/
2
/
4
4
2
× 1
× 1"
1
1
3
1
/
/
2
/
2
2
4
2 × 2 × 1"
N/A
Figure 1. Mounting dimensions:
3"
Tee Adapter
Tee Depth
Refer to
Tee Depth
Table
Installation Guidelines
Before
installing
thoroughly familiar with:
NFPA 72:
National Fire Alarm Code
NFPA 13:
Installation of Sprinkler Systems
NFPA 25:
Inspection, Testing, and Maintenance of
Water-based Fire Protection Systems
NFPA 13D:
Standard for 1 and 2 Family Dwellings and
Manufactured Homes
NFPA 13R:
Standard for Multi-family Dwellings
1
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
(See Figure 1)
CPVC/Spears CPVC/Central
"
"
"
3
1
15
1
/
N/A
2
/
2
/
4
4
"
"
1
2
/
N/A
N/A
N/A
6
"
"
"
1
1
2
/
2
/
N/A
N/A
4
2
"
3
2
/
N/A
N/A
N/A
4
"
3
3
/
4
(WFDT)
"
9
3
/
16
(WFDTH)
"
5
4
/
16
Gage (End of Paddle Tree)
Must Fit Between Top of
Tee and Bottom of Flange
Tee Fitting
Plastic Vane
any
waterflow
alarm
"
"
13
2
/
32
16
N/A
N/A
N/A
A78-1939-00
device,
be
I56-480-05R

Advertisement

loading
Need help?

Need help?

Do you have a question about the System Sensor WFDT and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Pittway System Sensor WFDT

  • Page 1 INSTALLATION AND MAINTENANCE INSTRUCTIONS WFDT/WFDTH Vane-type A Division of Pittway 3825 Ohio Avenue, St. Charles, Illinois 60174 Waterflow Detectors 1-800-SENSOR2, FAX: 630-377-6495 Specifications Contact Ratings: Two sets of SPDT (Form C) 10 A @ 125/250 VAC; 2.5 A @ 24 VDC...
  • Page 2 Figure 2. Assembly diagram: 2. WFDT and WFDTH units are shipped without paddles mounted to the actuator. Select the correct size paddle for the type of tee being used. Align hole on stem of COVER paddle with hole on actuator lever. Fasten together using TAMPER PROOF a #4-40 x 1/4"...
  • Page 3 Figure 3. Field wiring: Top View NOTE: Common and B connections will close when vane is deflected, i.e., Switch 1 when water is flowing. Dual switches permit applications to be combined on a single detector. CONTACT RATINGS Switch 2 125/250 VAC 10 AMPS 24 VDC 2.5 AMPS...
  • Page 4 replacement kits are available. To replace the delay Operational Testing Always notify a central station monitoring waterflow mechanism, request Part No. A3008-00; for switch alarms before repairing, maintaining or testing waterflow enclosure, request Part A77-01-02. Complete alarm devices. instructions are enclosed with each. Either mechanism can 1.

This manual is also suitable for:

System sensor wfdth