—TROUBLESHOOTING—

No Fog:
Check for motor rotation. If motor is operating properly, there will be
an adequate amount of water in the pan (1/4" to 1-1/4").
If the pan runs dry, the float valve may be sticking in the up posi-
tion. If so, the inlet water pressure needs to be reduced. If water
supply is adequate, check the tapered pump for internal calcium
build-up. Remove, inspect and clean as needed.
Overflowing Pan:
An overfilled pan can cause poor quality fog and wetness around
the unit.
A leaky float valve or a float that has filled with water may be the
problem. To check the float, raise it out of the water and visually
inspect it. No water should be inside and it should not sink.
If OK, then check for leaky valve. Turn water off and remove the
fogger from the pan.
Empty the pan and towel dry. Hold the float in the up position and
turn on the water.
If any water enters the pan while the float is in the up position, the
float valve needs to be replaced.
IDEAL-AIR™
PRODUCT# 700860