Wiring between indoor unit and outdoor units
NOTE
A wiring diagram below is an example for connection to SMMS-u series. For connecting to other outdoor unit
series, refer to the Installation Manual attached to the outdoor unit to be connected.
Wiring example
Outdoor Power supply
380V - 415V ~, 50 Hz
380V ~, 60 Hz
Circuit breaker
Outdoor unit
Header outdoor
Earth
terminal
S: The ground of a
shielded wire
Control wiring between indoor and outdoor units (Shield wire)
Control wiring between indoor units (Shield wire)
Indoor unit
Indoor unit
Earth
Earth
Indoor power supply
220V - 240V ~, 50 Hz
Remote controller
208V - 230V ~, 60 Hz
Circuit breaker,
Pull box
Power switch
35-EN
Outdoor Power supply
380V - 415V ~, 50 Hz
380V ~, 60 Hz
Circuit breaker
Outdoor unit
Follower outdoor
Earth
terminal
S: The ground of a shielded wire
Control wiring between outdoor units (Shield wire)
Indoor unit
Indoor unit
Earth
Earth
Remote controller
Remote controller
Pull box
Pull box
Group control
Wire connection
REQUIREMENT
• Connect the wires matching the terminal numbers. Incorrect connection causes a trouble.
• Pass the wires through the bushing of wire connection holes of the indoor unit.
• Keep a margin (Approx. 100 mm) on a wire to hang down the electrical control box at servicing or other purpose.
• The low-voltage circuit is provided for the remote controller. (Do not connect the high-voltage circuit)
Before performing wiring work in the electrical control box, remove the
cover of the box (fixed with 2 screws).
Remove screw A, and loosen screw B.
Pull up the electrical control box cover and then open it forward.
Tighten the screws of the terminal block firmly, and fix the wires with
the cord clamps attached to the electrical control box.
(Do not apply tension to the connecting section of the terminal block.)
Slide the electrical control box cover to install it. Do not pinch the wire
too strong, and reduce the load on the wire. Make the gap as small as
possible when installing the cover.
U
(U
v
1
Cord clamp
L
N
Remote controller
wiring
Earth screw
System interconnection
wire
R
S
(L)
(N)
Earth wire
System interconnection wire
Remote controller wiring
Strip off approx. 9 mm the wire to be connected.
Wiring diagram
Terminal block for remote
Terminal block
controller wiring of indoor unit
A
B
Remote controller wire
(Locally procured)
– 18 –
Electrical control
box cover
Side D (Space: 8.5 mm)
Side C (Space: 4 mm)
A
B
)
U
(U
)
v
2
Select side C or D for the power cable clamping position referring to
the following table according to the cable type and diameter.
* The cord clamp can be attached on either right or left side.
Clamp two cords side-by-side for twin connection.
Wire type
Specification
3-core stranded wire 2.5 mm²
Cabtyre cord
4-core stranded wire 1.5 mm²
See the figure on the left for
system interconnection wires to
the terminal block.
System interconnection wire
Remote
A
controller
B
unit
Loosen screw B.
1
2
Remove screw A.
Cable clamping position
Side D
Side C
EN
ID
ID
36-EN