Download Print this page

Haneco DUET4W Manual

Lighting twin head emergency led floodlight

Advertisement

Quick Links

HANECO LIGHTING TWIN HEAD EMERGENCY LED FLOODLIGHT
Thanks for choosing our DUET4W products.
We strongly recommend that you read this manual carefully before installation.
Product Specifications
MAX POWER
PRODUCT
CONSUMPTION
CODE
( WHEN CHARGING )
DUET4W
4.5W
The Haneco DUET Surface Mount Non-Maintained Emergency LED Floodlight can be installed on plaster walls or solid block surfaces.
The DUET4W comes with a 1.2m flex and plug for easy power connection.
Testings
The Haneco DUET4W must be allowed to charge the battery for 16 hours when the fitting is connected to un-switched active prior to
operation. The product shall be tested in accordance to the instructions below:
1. Operational test
Press and hold test button or switch off power, check that both lamps are on.
Release the test button or switch on power, check that both lamps are off.
2. Duration test
Press test button once and check that both lamps remain on for at least 2 hours after the first installation (and at least 1.5 hours for
the following tests). All test results must be recorded in a service logbook that should be kept on-site at all time. Should the unit fail
the test, remedial action must be taken.
For any malfunction such as indicator failure, lamp not illuminated in EM mode or not illuminated for more than 1.5 hours, please check:
Main power is connected, and turned on.
Battery is connected.
Battery, test switch and lamp head for any damage.
Battery has been allowed to charge for at least 16 hours.
Attention!
Power circuits may not be powered on most building sites in Australia during construction.
Fittings on these circuits will have their batteries or power storage units discharged.
The LiFePO4 battery of Haneco DUET is designed to perform an excellent long-life in a controlled AS/NZS 60598.2.22 testing environment.
Excessive battery discharging would reduce this performance and cause battery failures.
Battery warranty claims as a result of such abuse are specifically excluded from Haneco warranty terms.
DUET 4W
IP
INPUT
RATING
RATING
220 – 240Va.c.
IP20
50/60Hz
For more information
www.haneco.com.au
1300 001 LED (533)
OPERATING
ELECTRICAL
TEMPERATURE
CLASSIFICATION
0-45°
Class II
EM
TIME
>1.5hr

Advertisement

loading

Summary of Contents for Haneco DUET4W

  • Page 1 The DUET4W comes with a 1.2m flex and plug for easy power connection. Testings The Haneco DUET4W must be allowed to charge the battery for 16 hours when the fitting is connected to un-switched active prior to operation. The product shall be tested in accordance to the instructions below: 1.
  • Page 2 HANECO LIGHTING TWIN HEAD EMERGENCY LED FLOODLIGHT DUET Installation Instructions Fix four screws on the installation surface. Switch-off main power. 257mm 107mm Put product on the mounting surface, adjust until Connect the fitting to main by either of the following two ways: fitting can sit stable on the mounting screws.