Technical Data - Jetter JetWeb JX2-SIM8 Operator's Manual

Table of Contents

Advertisement

JX2-SIM8
4
Caution
Jetter AG

Technical Data

Technical Data - JX2-SIM8 Module
8 digital inputs
Type of inputs
Power Supply
Connection to the basic unit via
system bus
Input terminals
LEDs, inputs 1-8
Enclosure
Dimensions (H x W x D in mm)
Weight
Mounting
Heat loss of logic circuit
Rated Input Voltage
Voltage Range
Input current
Input resistance
Input delay time
Signal voltage ON
Signal voltage OFF
Signal processing
Electrical Isolation
Make sure that digital input modules are disconnected from the supply before
inserting or removing them. When removing or inserting the module, the supply
lines as well as the signal lines must be de-energised. Otherwise the JX2-SIM8
module will be destroyed.
DC 24 V -15 % .. +20 %
Inputs 1 to 4: Pushbuttons
Inputs 5 to 8: Switches
centralised arrangement: via basic unit
decentralised arrangement: via power
supply module JX2-PS1.
Male connector SUB-D, 9 pins
Plug-in terminal blocks
DC 24 V are applied to the input. Pick-off
method: Hardware-triggered signal
Aluminium, painted
115 x 45 x 69
350 g
DIN Rail
0.3 Watt
DC 24 V -15 % .. +20 %
DC 0 .. 30 V
approx. 8 mA
3.0 kΩ
approx. 3 ms (from 0 to 1, and from 1 to 0)
min. DC 11 V
max. DC 5 V
dynamic
None
4 Technical Data
17