JX2-SIM8
3
Jetter AG

Operating Parameters

Environmental Operating Parameters
Parameter
Operating Tempera-
ture Range
Storage Temperature
Range
Air Humidity / Humid-
ity Rating
Pollution Degree
Corrosion Immunity/
Chemical Resistance
Operating Altitude
Mechanical Operating Parameters
Parameter
Free Falls Withstand-
ing Test
Vibration Resistance
Shock Resistance
Degree of Protection
Mounting Position
Value
0 °C through 50 °C
-25 °C through +70 °C
5 % to 95 %
No condensing
2
No special protection against
corrosion. Ambient air must be
free from higher concentrations
of acids, alcaline solutions, cor-
rosive agents, salts, metal va-
pours, or other corrosive or elec-
troconductive contaminants.
Up to 2000 m above sea level
Value
Height of fall (units within pack-
ing): 1 m
10 Hz - 57 Hz: with an amplitude
of 0.0375 mm for continuous op-
eration (peak amplitude of 0.075
mm)
57 Hz -150 Hz: 0.5 g constant
acceleration for continuous op-
eration (1 g constant accelera-
tion as peak value), 1 octave per
minute, 10 frequency sweeps
(sinusoidal), all spatial axes
15 g occasionally, 11 ms, sinu-
soidal half-wave, 2 shocks in all
three spatial axes
IP20, rear: IP10
Any position, snapped on DIN
Rail
3 Operating Parameters
Reference
DIN EN 61131-2
DIN EN 60068-2-1
DIN EN 60068-2-2
DIN EN 61131-2
DIN EN 61131-2
DIN EN 61131-2
Reference
DIN EN 61131-2
DIN EN 60068-2-32
DIN EN 61131-2
IEC 68-2-6
DIN EN 61131-2
IEC 68-2-27
DIN EN 60529
13