General Description
The TC-110 series panel mount temperature controllers provide
temperature display, relay control, and feature programmable
setpoints, upper and lower setpoint limits, differentials and
calibration.
Applications
Applications include heating, cooling, refrigeration, HVAC,
food service, medical and industrial equipment.
Features
• Membrane touch-pad programming
• 0.56" high red LED display
• Programmable setpoint(s) and differential(s)
• Panel mount enclosure
Specifications
Power requirements: Available in 12 or 24 volt models -
Specify AC (2VA) or DC (100 mA) voltage supply
Accuracy: +1°F, +1°C
Relay status indicator: Lighted while relay is activated
Relay(s) contact rating: SPDT relay, 4 Amp
(24 VAC resistive).
Series
Temperature Range °F / °C
110/111
–67° to 302°F / –55° to 150°C
110H/111H
32° to 572°F / 0° to 300°C
110RTD/111RTD
–99° to 999°F / –72° to 538°C
Dimensions & Wiring
relay status indicator
1.51"
ADJUST
(38 mm)
3.22"
(82 mm)
N0 C NC NO C NC G S +5 –3 – +
SP-2
SP-1
1724 Lake Drive West • Minneapolis, MN 55317 • 612-448-2217 FAX 612-448-1606 • Made in USA
Custom Design
Innovative Technologies in Custom Electronic Design & Manufacturing
Accuracy
+1°F/1°C
+ 2°F/1°C
+ 2°F/1°C
(over 300° span)
0.125"
(3 mm)
hidden
°F
button
1.27"
(32 mm)
SET
+ = volt (white)
Input
Power
– = ground (black)
+5 = factory
Factoryy
–3 = factory
Temperature Controllers
• Temperature setpoint display
• LED relay status indicator(s)
• Tamper resistant programmable setpoint limits
• Available with single or dual stages
Ambient temperature range: 20° to 158°F,
– 6° to 70°C
Humidity: 90% non-condensing
Agency approvals: U.L. and C.U.L. recognized,
NSF listed depending on model (consult factory)
Weight: 3.6 oz. (1.64kg)
Sensor Type
PTC, 0.25"OD x 1.75" nickel plated copper cap, 36" two
conductor 24 AWG wire (included)
PTC, 0.188"OD x 4" stainless steel cap, 36" two conductor
24 AWG wire (included)
100 ohm platinum RTD (not included)
1.51"
(38 mm)
2.533"
(64 mm)
Sensor , TC - 110
Sensor , TC - 110H
(polarity sensitive)
Sensor , TC - 110 RTD (no polarity)
TC–110
TC–110H
TC–110RTD
Cutout Dimensions
(34 mm)
3.1"
(79 mm)
G = ground (black)
S = signal (white)
G = ground (white)
S = signal (red)
1.35"