Page 1
The Boiler Reset Module 420 provides outdoor reset to a hydronic heating system in order to maximize comfort and efficiency. The 420 can operate a single on / off boiler or a single modulating boiler. The 420 can override the outdoor reset water temperature to provide Domestic Hot Water or Setpoint operations.
Do not apply power Use the Lock / Unlock DIP switch to lock and unlock the Access Boiler Reset Module 420 Menu Level of the 420 and all connected tN4 devices, including tN4 thermostats. For details, see “Access Levels” Item tektra 991-01...
Use the tekmar Stager / Off DIP switch when a tekmar control operates an On-Off boiler or the firing rate of a staging control is be connected to the 420 in order to Modulating boiler. operate multiple boilers. A tekmar stager may include Boiler Controls 264, 265, and 268.
Item, Up, Down) to select settings. As you enter settings, 1. Select the appropriate menu using the Menu button. record the settings in the Job Record J 420. 2. Select the item using the Item button. 3. Use the Up or Down button to make the adjustment.
IF the On-Off / Modulating DIP switch is set to Modulating Access to the Test button requires the removal of the or the tekmar Stager / Off DIP switch is set to tekmar front cover and exposes hazardous voltage while the Stager: control is powered.
Outdoor Reset Module (thermostats, Reset Module and Expansion Modules). Each The Boiler Reset Module 420 is the system control for a tN4 device is connected to a tN4 communication bus using hydronic heating system. The 420 operates a single heat two wires.
• • Locate the Boiler Design setting in the Adjust menu. Boiler Temperature Control Section C The 420 is able to operate a single, hot water, on-off or menu. If the control does not presently have a requirement modulating boiler as a heat source. For proper operation of for heat, it does not show a boiler target temperature.
Page 15
• • Locate the Fire Delay setting in the Adjust menu. The 420 can operate a single hot-water modulating boiler. This requires the use of the Mod (dc) output on the 420. Boiler Contact Closed To operate a modulating boiler, the Boil On - Off / Mod DIP switch must be set to Mod.
Page 16
Example: For boilers with electronic operators, the boiler’s input A boiler’s input signal range is 2 - 9 V (dc). The 420 control signal range may not match the output signal range of has an output signal range of 0 - 10 V (dc).
Control 264, 265, or 268. The 420 uses the modulating 1. Set the 420 Off / tekmar Stager DIP switch to tekmar output to provide a 0 - 10 V (dc) signal to the external input Stager.
No voltage present on demand Test voltage across demand terminals terminals. using voltmeter. Control in Unoccupied and DHW Check which schedule the 420 is Unoccupied or Setpoint Unoccupied Boiler does not fire when there is a operating on. set to OFF.
Purchaser shall indem- such Product sale and acknowledges that it has read nify and hold tekmar harmless from and against any and all and understands same. claims, liabilities and damages of any kind or nature which...