Descrip On Of Opera Ng Eka Nis; Descrip On Of Opera Ng Eka Nv; Descrip On Of Opera Ng Eka Ni - Ventmatika EKA Technical Data Manual

Electrical circular duct heaters
Table of Contents

Advertisement

Descrip on of opera ng EKA NIS ...

Electrical duct heaters EKA NIS ... are designed for the heaters power (0...100) % control by analog signal input
(0...10) VDC.
When the heater power supply is switched on, LED 6 on the controller (EKR-K...) PCB (see Fig. 1 on page 4)
flashes every second. If controller turns on the hea ng depending on analog signal, LED 5 lights (see Fig. 1 on page
4).
Descrip on of opera ng EKA NV ... (PTC...PS)
Electrical duct heaters EKA NV ... (PTC...PS) are designed with integrated temperature control, PTC (air
velocity), PS (air pressure) and temperature sensors, setpoint poten ometer knob is integrated on the heater lid.
When the heater power supply is switched on, controller (EKR-K...) is in prepara on mode for 30 seconds, LED
1 flashes once every 5 seconds. If air velocity is detected by PTC sensor (rapid LED 1 flashes when Min. 1,5 m/s is
detected) and air pressure is greater than min 20kPA a er prepara on mode ends, LED 1 will start to flash once
every second and controller will ini ate the hea ng based on demand, LED 2 is indica ng when hea ng is ini ated.
If there is no air velocity detected and or there is not enough pressure in the duct, controller will not ini ate the
hea ng un l air velocity and or pressure is detected. Heaters EKA NV... (PTC...PS) operates by the supply (TJ-K10K)
air temperature sensor.
EKA NV ... PTC ... setpoint temperature (0...30) °C
EKA NV ... PTC/PS setpoint temperature (-10...50) °C
There can be set the different desired (setpoint) air temperature by poten ometer on the top of the heater
casing.
Pre-heater casing and air duct before pre-heater should be insulated with rock wool 10cm (R~2,4m²K/W).
Depending on the moun ng posi on of the heater in the duct rela ve to the motor (pre- or post-motor), the
pressure hose must be placed on the "-" or "+" pipe, respec vely.
IMPORTANT: If failure appears, power supply must be switched off and only then performed fault
elimina on works.
Descrip on of opera ng EKA NI ... (PTC...PS)*
Electrical duct heaters EKA NI ... (PTC...PS) are designed with integrated temperature control, PTC (air velocity)
PS (air pressure) and temperature sensors, wired remote control panel (TR5K) for temperature setpoint.
When the heater power supply is switched on, controller (EKR-K...) is in prepara on mode for 30 seconds, LED
1 flashes once every 5 seconds. If air velocity is detected by PTC sensor (rapid LED 1 flashes when Min. 1,5 m/s is
detected) and air pressure is greater than min 20kPA a er prepara on mode ends, LED 1 will start to flash once
every second and controller will ini ate the hea ng based on demand, LED 2 is indica ng when hea ng is ini ated.
If there is no air velocity detected and or there is not enough pressure in the duct, controller will not ini ate the
hea ng un l air velocity and or pressure is detected.
Heaters EKA NI ... (PTC...PS) operates by the supply (TJ-K10K) air temperature sensor.
EKA NI ... PTC ... setpoint temperature (0...30) °C
EKA NI ... PTC/PS setpoint temperature (-10...50) °C
There can be set the different desired (setpoint) air temperature by wired remote control panel.
Pre-heater casing and air duct before pre-heater should be insulated with rock wool 10cm (R~2,4m²K/W).
Depending on the moun ng posi on of the heater in the duct rela ve to the motor (pre- or post-motor), the
pressure hose must be placed on the "-" or "+" pipe, respec vely.
IMPORTANT: If failure appears, power supply must be switched off and only then performed fault
elimina on works.
* - non standard op on. For more informa on please contact sales@ventma ka.lt