ELECTRICAL CIRCULAR DUCT HEATERS Description Electrical duct heaters EKA are designed to heat fresh air in ventilation systems. Casing (EKA protection class IP 44, except EKA Type NV which protection class IP 30) is made from Aluzinc coated steel which is high temperature proof and with rubber seals for duct connection. Heating elements tube is made from stainless steel AISI 304.
Page 7
ELECTRICAL CIRCULAR DUCT HEATERS Model marking EKA 100-0.3-1f PS without integrated control 1 – Duct diameter (mm) – 100 mm – 200 mm – 355 mm – 500 mm – 125 mm – 250 mm – 400 mm – 160 mm –...
Page 8
ELECTRICAL CIRCULAR DUCT HEATERS 5 – Additional accessories: – Differential pressure switch for air flow detection – Sensor for minimum air velocity detection PTC/PS – Sensor for minimum air velocity detection and diff. pressure switch for air flow detection PTC/K –...
Page 9
ELECTRICAL CIRCULAR DUCT HEATERS IMPORTANT: The installation to the mains power supply may only be wired by a competent electrician. The power supply cable must be selected in the ratio with power of the heater. When installing these heaters, the standards and regulations in force in your country must be followed strictly adhered to. Within the installation an electrical isolation automatic circuit breaker (not included) must be present, to enable the installer to cut all power supply lines.
Page 10
ELECTRICAL CIRCULAR DUCT HEATERS Fig. 3. Mounting example EKA NIS… Fig. 4. Mounting example EKA ESKM… Fig. 5. Mounting example EKA NV…2NTC… Fig. 6. Mounting example EKA NI…2NTC…...
Page 11
ELECTRICAL CIRCULAR DUCT HEATERS AHU – Air handling unit Fig. 7. Mounting example EKA NV… (Preheater) AHU – Air handling unit Fig. 8. Mounting example EKA NI… (Preheater) AHU – Air handling unit Fig. 9. Mounting example EKA NIS… (Preheater) AHU –...
Page 12
ELECTRICAL CIRCULAR DUCT HEATERS Heaters EKA with integrated controller Heaters EKA with integrated temperature controller EKR-KN… (See Fig. 11) can be controlled in five different ways depending on control type: Type EKA NV – temperature control potentiometer on the top of the heater casing for Type EKA NI –...
Page 13
ELECTRICAL CIRCULAR DUCT HEATERS External controllers for the heaters EKA Heaters EKA without integrated control can be controlled with external controllers (listed below) with one or two air temperature sensors (ordered separately), depending on operating mode. Voltage Controlled Additional Controlled Total load Type Input/Output...
Page 14
ELECTRICAL CIRCULAR DUCT HEATERS Additional accessories for the controllers Additional accessories (ordered separately) intended for use with external and integrated controllers are listed below: Measurement range Setpoint range Type Description (°C) (°C) Duct temperature -30...105 sensor TJ-K10K Room temperature -30...105 sensor panel TR NTC10 Room temperature...
Page 15
ELECTRICAL CIRCULAR DUCT HEATERS Description of control type Heater type Temperature control type Setpoint range EKA NV... Potentiometer on the top of the heater casing (0...30) °C* EKA NI... External wired remote panel with setpoint knob (TR5K) (0...30) °C EKA NIS... External wired remote (0...10) VDC signal (analog input) P**×(0...100) % EKA ESKM...
Page 16
ELECTRICAL CIRCULAR DUCT HEATERS IMPORTANT: If failure appears, power supply must be switched off and only then performed fault elimination works. Description of operating EKA NIS … Electrical duct heaters EKA NIS … are designed for the heaters power (0…100) % control by analog signal input (0…10) VDC.
Page 17
ELECTRICAL CIRCULAR DUCT HEATERS Heaters EKA NI … PTC … (PH) operates by the supply (TJ-K10K) air temperature sensor. Setpoint temperature (0…30) °C. There can be set the different desired (setpoint) air temperature by wired remote control panel. If LED 1 lights continuously it means that there is a failure of: PTC (air velocity) sensor, supply (TJ-K10K) air temperature sensor, wired remote control panel TR5K.
Page 18
ELECTRICAL CIRCULAR DUCT HEATERS IMPORTANT: If failure appears, power supply must be switched off and only then performed fault elimination works. Description of operating EKA NI … 2NTC Electrical duct heaters EKA NI … 2NTC are designed with integrated temperature control, two temperature sensors, wired remote control panel (TR5K NTC10) for temperature setpoint.
Page 19
ELECTRICAL CIRCULAR DUCT HEATERS If LED 1 lights continuously it means that there is a failure of: PTC (air velocity) sensor, supply (TJ-K10K) or room (NTC10) air temperature sensor, potentiometer on the top of the heater casing. When the heater power supply is switched on, after power supply interruption or after any failure, controller is in preparing mode for 30 seconds.
Page 20
ELECTRICAL CIRCULAR DUCT HEATERS Description of operating EKA MB … Electrical duct heaters EKA MB … can communicate via Modbus RTU. Connected to the system EKA MB … is a Slave device. Modbus settings are shown in table 2. Table 2. Modbus settings Setting Possible values Default value...
Page 21
ELECTRICAL CIRCULAR DUCT HEATERS Electrical wiring diagrams S – Automatic circuit breaker J – Switch T – Timer EKR-KN… – PCB of temperature controller V1, V2 – Triacs A – Heating elements B – Overheat thermostat with automatic reset C – Overheat thermostat with manual reset K –...
Page 58
For warranty service, contact an official “Ventmatika“ dealer. Any manipulation of the appliance by personnel not appointed by “Ventmatika“ will cancel the guarantee. “Ventmatika“ reserves the right to modify the product without prior notice.