1. General 1.1 Introduction of ATEX ATEX is an acronym of “Atmosphéochres Explosives” from French. This includes two European Union (EU) directives which regulate the manufacture, selection and usage of equipments in dangerous zone and has become a compulsory act between members of EU since July 2003.
management system, and each product can reach the same standard as an EU model tested sample. According to different conditions of conformity assessment the appendix of ATEX 2014/34/EU also regulates corresponding QA requirements. The confirmation of requirement of the above mentioned QA system is supervised by EU designated authorities, and the so called QA system is not only the field covered by ISO 9001.
Page 5
(>450 (>300 (>200 (>135 (>100 (>85 Methane II A Acetic acid Ethanol Gasoline Acetaldehyde Ammonia 1,4 Butane Diesel Benzene Butanol Kerosene Propanone Fuel oil Ethane Hexane Ethyl acetate Carbon monoxide Methanol Propane Methylbenzene II B Coal gas Ethylene Diethyl ether II C Hydrogen Acetylene...
2. Specifications and description of design 2.1 Compressor Nomenclature R C 2 – x x x x Explosion proof products Displacement at 50Hz RC model 2 version 2.2 Compressor outline RC2-100ExP/140 ExP A/B...
2.4 Available refrigerants for compressors Available refrigerants for Hanbell compressors are included A1, A2, A3 in ASHRAE 15, and the refrigerant of working conditions corresponding to the use of pressure must not exceed 28kg/cm G. Please contact Hanbell directly if refrigerant is excluding on the list of ASHRAE 15 or not included in the scope of the refrigerant A1 to A3.
400 N-m Table 2.1 cable glands and plugs tightening torque Hanbell selection software provides working current and MCC based on the working condition, which can be the reference for selecting electric wiring, magnetic contactor, and fuse. The anti-loose connector can prevent the compressor from sudden motor trip due to motor protector error.
The Ex cable entry of cable box must installed at least by ATEX certified cable glands. It is required to ensure that all bolts, plugs and cable glands are sealed in Ex cable box to avoid malfunction. ※ Sealant can be used LOCTITE 554 or similar nature of glue, but according to EN 60079-14 standard can’t using the tape seal.
Alarm lamp for this protector is required to be embedded on control panel as indicator. Any intention to short controllers for starting of compressors is prohibited. It is beyond Hanbell’s warranty of compressors if there is any action above mentioned found.
In addition, Hanbell also offers 250W oil heater to keep adequate lubricant oil temperature for large external oil separator and applications in areas with low ambient temperature. Specification: 250W; 110V or 220V; IP 54; Outer diameter of cable: 6~8mm Note: If compressor is installed in low ambient temperature, it is recommended to insulate oil separator against cold ambience.
Note: Before using oil drain valve, the compressor must be switched off and the refrigerant must be recovered completely to avoid dangerous leakage of refrigerant which threats the environment. 2.13 Solenoid valve Figure Solenoid valve Degree of protection IP 67 -40℃~+65℃...
Page 32
Percent voltage unbalance = 100 x NEMA states that poly-phase motors shall operate successfully under running conditions at rated load when voltage unbalance at the motor terminals does not exceed 1%. Furthermore, operation of a motor with over 5% unbalance is not recommended for it probably results in motor damage.
To solve this problem, use of oil heaters can warm up oil before starting. If the compressor operates under critical operating conditions, an extra oil cooler is required – please refer to Hanbell selection software for the required capacity and oil flow of the extra oil cooler. High-viscosity oil is recommended to apply in high operating conditions because high discharge temperature will make viscosity of oil lower.
Check acidity of oil after 72 hours of operation and then change it again until acidity of oil becomes normal. 5. Please contact Hanbell local distributors/agents for selection of oil. 3.3 Oil change 1.
4.1 Compressor lifting Each HANBELL screw compressor has been carefully tested at the factory and every precautionary measures have been taken to make sure that compressors will keep in perfect condition when reach customers’ work. After the compressor arrives at your warehouse, please check if its crate is kept in good condition and check all the compressor accessories with shipping documents to see if there is any discrepancy.
Page 37
If a large-caliber copper tube is not easily accessible and a steel tube is used instead in suction port, Hanbell also recommends the use of a copper tube in discharge port to best minimize abnormal vibration and noise.
Note: The accessory table is just for reference only. Actual specification and accessories enclosed might vary with different quotation and agreement respectively. If any optional accessory is required and out of above mentioned standard accessory, please contact Hanbell for detailed specification and price.
Page 39
Suction and discharge check valve Hanbell standard check valve (vertical type) is gravity-driven with characteristics of large flow volume and low pressure differential. After shut-down of compressor, Teflon taper guider inside can simultaneously seal up the precisely machined base of check valve by gravity force to effectively prevent return of high-pressured gas to compressor.
Page 40
Note: The above table lists specification of standard bushing for every model of Hanbell compressors. Their dimensions correspond to flange bushing dimensions and the table below. If bushing dimensions are not indicated in purchasing order, Hanbell will provide standard type. Suitable piping of customers’ choice is also shown in the table below. If non-standard bushing is needed,...
Page 41
141.3 f. Suction and discharge stop valves For maintenance and service of compressor, it is recommended to install the suction and discharge stop valves. Please refer to following detail of Hanbell stop valves. Stop Valve Size Stop Valve Size Model...
10% to the rated voltage. motor between phase to phase and Standard voltage is 220V. Maximum voltage is 230V. phase to ground. If there is other demand, contact HANBELL. Power terminals and wire cables’ Ω Insulation resistance value should be above 5M terminals connection.
Page 43
20K above the saturated condensing temperature and the suction vapor superheat should be within 10K to the saturated evaporating temperature. i. The whole plant, especially the pipelines and capillary tubes must be checked for abnormal vibrations. Please contact HANBELL or local distributor if any abnormal vibrations or noise found while compressor is running.
5.2 regular check a. To avoid refrigerant leakage, Hanbell strongly recommends using a gas detector and refer to ASHRAE 15 regarding standard leakage rate. b. Check whether clear frozen oil. 5.3 Troubleshooting The table below shows some problem that might encounter in the jobsite during commissioning or upon operation of compressor.
HANBELL screw compressor or it should be a Service Engineer from HANBELL. 5.4 Compressor checking list Please fill out the compressor checking list and send it to Hanbell, if any failure of compressor happened. Hanbell will reply and suggest the solution to resolve the failure.