Resetting the Ground Fault
Interrupt
This control panel is equipped with a ground fault inter-
rupt (GFPE) circuit breaker (Fig 6). If the disconnect
switch is ON, but all lights on the electrical control panel
are off, have a qualified electrician check the ground
.
fault interrupt
WARNING
ELECTROCUTION HAZARD
To reduce risk of injury or damage to
equipment, perform this procedure with the
main disconnect OFF.
GFPE
F
. 6
IG
14
Operation
TI0565
4-Zone Accessory Control
243699
To reset the ground fault interrupt, have a qualified elec-
trician:
1. Turn OFF the electrical disconnect on the electrical
control panel.
2. Open the electrical control box and locate the
Ground Fault Interrupt switch (GFPE). The ground
fault interrupt will be in a "neutral" position, between
the ON and OFF positions.
3. Move the GFPE switch to the OFF position, then
move it to the ON position.
4. Close the door and turn ON the disconnect switch.
2-Zone Accessory Control
243698
TI0561
309213G
TI0562