1. Feature
Used as an warning device to generate fire alarm;
Installation and wiring same as detector base;
Driven by detection circuit, no need for extra power
line.Two adjustable modes, sharing the same address
of detector, or occupying an individual address.
Description
2.
VG-6617S Digital Alert Base is designed for the application inside a closed room. As a warning
device, the base will generate alarm sound when the detector detects a fire occurred. Installed as a
base, it is compatible with the range of digital detectors. For application, when sharing the same
address with detector, the alert base will be triggered by that detector installed. Setting with an
individual address, the alert base can be as used a field warning device and activated by C&E Logic.
It is usually installed in hotel room, residential bedroom or other locations that are far away from the
audible and visual alarm..
3. Technical Data
Operating voltage:
Operating current:
Address
Sound level
Tonal modification cycle
Temperature:
Relative humidity
Weight
Shell material and color
Dimension
Installation hole distance
Wiring: directly connected with the detection loop of the control panel.
Loop voltage: 24V /Allowance range: 15V~28V (Vp-p)
Standby current: ≤ 0.2mA
Action current: ≤ 3mA
Total starting current at alarm state both for the detector and
alert base ≤ 3.5mA (maximum 20 pieces triggered at exactly
≤95%,non-condensing
ABS+PC, White
diameter of 102mm, height of 25.5mm
1
VG-6617S Digital Alert Base
Installation and Operation Manual V1.00
the same time)
1~254
>75dB
0.6~1.5S
-10℃~+55℃
67g
73mm
Base
VSL3.928.011VGASY