“VALIDATING AND ADJUSTING VENTILATION SYSTEMS” MANUAL The FlowFinder mk2® is the successor of the well known FlowFinder 153, which has proven itself as the benchmark for air flow measurements to balance mechanical air supply and exhaust systems. The new FlowFinder mk2® is fully zero pressure compensated...
18. NOTES Despite the fact that this manual has been carefully put together by ACIN instrumenten bv, no responsibility is accepted for any errors in the manual and possible consequences. We are obviously very interested in your comments and additions.
2. Transport case (with key) present. Avoid lifting the FlowFinder mk2® 3. Battery pack (mounted onto the while holding onto a hood. FlowFinder mk2®, or stored in the case) 4. Battery charger 5. Hood 230x230x145mm 6. Hood 600x600mm (optional) 7. MicroSD card, USB adapter, SD adapter 2.
One can then adjust the ventilation system while measuring. Important: When the FlowFinder mk2® is stored away for a longer period of time one should store the battery pack separately, after having it charged first. Extra battery packs can be ordered from ACIN. 19-11-2013...
Below the unit of flow is a bar that during a measurement will fill up in green, the length of the green bar is proportional to the airflow. When the FlowFinder mk2® is in rest and in measuring mode, you will find below this bar a: 1. blinking ‘0’...
Leave this menu by pressing the white arrow again. The Options menu appears again. 5. Choose Validate or Adjust as default start up measurement of the FlowFinder mk2® 6. Set the Date: 7. Set the Time: 6.1 Press date Press time 6.2 Enter the year (yyyy)
‘validate’ or ‘adjust’. To change the default mode you have to go to the options menu. To do a measurement, hold the FlowFinder mk2® by the left and right round handles and place the instrument over the outlet or inlet you want to measure. Make sure to make a tight connection by pushing enough to avoid measuring secondary air.
9. ADDING OF MEASUREMENTS Thanks to the zero pressure compensation of the FlowFinder mk2®, it is possible to measure the air flow at part of the diffuser. Because the FlowFinder mk2® actively compensates its own resistance, the flow through the other (free) part of the diffuser will not or hardly be influenced.
11. PROCESSING THE STORED DATA 1. Turn off the FF-mk2® 2. Remove the micro-SD card by pushing on it and then releasing it 3. Either the SD adapter or the USB adapter can be used to connect to your computer 4.
12. PROCESSING THE DATA IN EXCEL Turn off the FF-mk2® Remove the micro-SD card by pushing on it and then releasing it Either the SD adapter or the USB adapter can be used to connect to your computer When inserted a screen ‘Automatic…’ will pop up. Ignore this screen or click cancel. Open Excel Select ‘Data’, ‘From text’...