Summary of Contents for Groupe Atlantic MELBURY HE 3800
Page 1
Document No. 410821-V11 / 18.12.2020 MELBURY HE FR DE EN ES IT NL 3800 TO 10000 Installation, use and maintenance instructions CAUROIR SITE Route de Solesmes FR - 59400 CAUROIR...
Page 2
MELBURY HE 3800-10000 - Installation, Use and Maintenance Page 2 / 36 410821-V11...
MELBURY HE 3800-10000 - Installation, Use and Maintenance WARNINGS AND CONFORMITIES Symbols used in this document INFORMATION: This symbol highlights the remarks. Failure to follow these guidelines carries the risk of damage to the facility or to other CAUTION: objects.
MELBURY HE 3800-10000 - Installation, Use and Maintenance Packaging After removing all packaging materials, check the apparatus and contact the supplier. The packaging contents to make sure that no damage has occurred materials are to be disposed of properly.
MELBURY HE 3800-10000 - Installation, Use and Maintenance Water quality The following rules apply once the boiler is put into service and remain valid until the end of life of the product. Preparing the water system before putting the boiler into service...
Page 6
MELBURY HE 3800-10000 - Installation, Use and Maintenance - Internal pressure with the unit of more than 1 bar treatment questions to specialists, which can provide: cold. - The appropriate treatment based - Remove leaky (permeable) components that are characteristics of the unit, letting out more gas than as if they were sealed.
MELBURY HE 3800-10000 - Installation, Use and Maintenance as possible to ensure the highest service life. possible. The first heating must allow the evacuation of moisture Do not hesitate to adopt the burner's burner maintenance from concrete doors, it is necessary to avoid any heat...
MELBURY HE 3800-10000 - Installation, Use and Maintenance CONTENTS WARNINGS AND CONFORMITIES................3 Symbols used in this document ..........................3 Conformity ................................3 Environmental compatibility ........................... 3 Steps to be taken in case of danger ........................3 The boiler ................................3 Packaging ................................
Page 9
MELBURY HE 3800-10000 - Installation, Use and Maintenance 5. OPERATING CONDITIONS ..................30 5.1. Fuels ................................30 5.2. Combustion air ............................. 30 5.3. Filling the installation and water quality ......................30 5.4. Protection against corrosion ......................... 30 5.5. Requirements for operation .......................... 30 6.
In addition, the front opening for easy cleaning. part of the Melbury HE 3800-10000 boiler is provided A divided version of the boiler range can be made with superior quality ceramic fibre insulation. The available as custom made option.
MELBURY HE 3800-10000 - Installation, Use and Maintenance 2. DATA 2.1. Main data Melbury HE Max. operating pressure (standard model) 6,0 bar Test pressure (other pressures on request) 9,0 bar Boiler supply and return pipe flanges PN 6 Max. operating temperature (safety cut-out) 110 °C...
MELBURY HE 3800-10000 - Installation, Use and Maintenance 2.3. Dimensions Melbury HE 22297-B figure 2 – Melbury HE 3800-10000 Page 12 / 36 410821-V11...
MELBURY HE 3800-10000 - Installation, Use and Maintenance 2.4. Dimensions of custom made models for Melbury HE The following custom made models are available on request. They are however subject to different delivery times! 2.4.1. Vertical flue connection CAUTION: The vertical smoke nozzles are not made on the Melbury HE.
Page 15
MELBURY HE 3800-10000 - Installation, Use and Maintenance 2.4.2. Divided version Also available as a custom made option is a divided conditions are tight. The individual prefabricated parts version of the boiler. must be welded together in the boiler room.
MELBURY HE 3800-10000 - Installation, Use and Maintenance 2.4.3. Different operating pressures Melbury HE boilers can be provided for the operating range of 6 bar-g, but their weights are different and the pressures of 4, 8 and 10 bar-g. Their dimensions and...
Page 17
MELBURY HE 3800-10000 - Installation, Use and Maintenance 2.5.1. Melbury HE Technical specifications Melbury HE, fuel oil Melbury HE 3800 4500 5400 6300 7400 8600 10000 POWER Boiler nominal power qN max. 3800 4500 5400 6300 7400 8600 10000 (80/60°C) min.
Page 18
MELBURY HE 3800-10000 - Installation, Use and Maintenance Technical specifications Melbury HE, natural gas Melbury HE 3800 4500 5400 6300 7400 8600 10000 POWER Boiler nominal power qN max. 3800 4500 5400 6300 7400 8600 10000 (80/60°C) min. 1160 1473...
Page 19
MELBURY HE 3800-10000 - Installation, Use and Maintenance Technical specifications Melbury HE, heavy fuel Melbury HE 3800 4500 5400 6300 7400 8600 10000 POWER Boiler nominal power qN max. 3300 4000 4700 5600 6700 8100 9700 (80/60°C) Calorific power qF max.
MELBURY HE 3800-10000 - Installation, Use and Maintenance 2.6. Correction values for different operating conditions 2.6.1. Flue gas temperature correction values Average boiler water tm °C temperature Flue gas temperature ∆t K - 16 ± 0 + 16 + 24...
MELBURY HE 3800-10000 - Installation, Use and Maintenance 3. BOILER CONTROL PANEL For hot water installation: o Maximal operating temperature: 95°C when the boiler is managed by a Navistem B1000 ou B2000. INFORMATION: o Maximal operating temperature: 105°C if the regulation system is compatible with this work.
MELBURY HE 3800-10000 - Installation, Use and Maintenance 3.4. Heating regulators 3.4.1. RVS 46 regulator (optional on the NAVISTEM B2000 control panel) Regulator not included in the basic panel (sold as additional equipment) : - Slave heating regulator to control a mixer valve...
MELBURY HE 3800-10000 - Installation, Use and Maintenance 4. INSTALLATION GUIDE 4.1. Boiler room and boiler room ventilation The boiler room must be arranged in compliance with Minimum air requirement is 1.6 m /h for each kW of local regulations installation specifications.
Page 24
MELBURY HE 3800-10000 - Installation, Use and Maintenance 4.2.3. Boiler support It is possible to mount the boiler on vibration dampers caused by vibrations. (available as option) to reduce noise transmission figure 9 - With vibration dampers figure 10 - Without vibration dampers...
MELBURY HE 3800-10000 - Installation, Use and Maintenance 4.3. Hydraulic connection For the hydraulic connection of the heating system and A component-tested membrane safety valve must be water heaters– in particular with regards to technical used to reliably prevent the permitted operating safety devices such as safety valves, expansion tanks, overpressure in the water heater from being exceeded;...
MELBURY HE 3800-10000 - Installation, Use and Maintenance 4.4.3. Connecting the burner The electrical connections of the burner (power supply and control) are made by the customer in accordance with the requirements of the burner. 4.5. Turbulators Thanks to the turbulators, which are to be inserted in...
MELBURY HE 3800-10000 - Installation, Use and Maintenance 4.6. Connecting the burner 4.6.1. Burner mating dimensions / orientation possibilities for Melbury HE figure 12 - Burner mating dimensions for Melbury BE Melbury HE 3800 4500 5400 6300 7400 8600 10000...
Page 28
MELBURY HE 3800-10000 - Installation, Use and Maintenance 4.6.2. Burner assembly The front door of models Melbury HE 3800-10000 is most cases require a special flange. This intermediate provided with a norm-conform flange to fit the burner. flange and related screws must be ordered separately An additional intermediate flange may nevertheless be or supplied by the burner manufacturer.
MELBURY HE 3800-10000 - Installation, Use and Maintenance 4.7. Flue gas system The Melbury HE boilers have been developed using The pertinent rules of technology and good practice as the latest technologies. The perfect balance existing well as the country-specific regulations and valid between boiler and chimney ensures optimal fuel use standards must be observed.
MELBURY HE 3800-10000 - Installation, Use and Maintenance 5. OPERATING CONDITIONS 5.1. Fuels The Melbury HE boilers are designed for operation with fuel oil EL and natural gas. Models Melbury HE 3800-10000 can also be operated on heavy fuel. The use of other fuels such as for example biogas is only permitted with the express CAUTION: approval of the manufacturer.
MELBURY HE 3800-10000 - Installation, Use and Maintenance 6. OPERATION Read this section of the manual with great care and get Please also note the operating conditions described in an installer to explain the heat producing system in all chapter 5.
MELBURY HE 3800-10000 - Installation, Use and Maintenance 6.3. First steps to take in case of failure In the event of system operational failure, perform the checks in the table below. Also check the governor set- up. If the failure cannot be eliminated, call a reliable engineer or your support service.
MELBURY HE 3800-10000 - Installation, Use and Maintenance 7. MAINTENANCE To maintain the high degree of efficiency of the unit, it is specialist in accordance with the official regulations. necessary to service it regularly. Depending on the type Before performing any work on the unit, it must be...