Product Description; Overview Of The Ups Module's Front; Figure 1 Front Panel View; Figure 2 Terminal Block 1 - Wieland Wipos UPS 20-960 User Manual

Table of Contents

Advertisement

3 Product description

NOTE:
Use latest device Documentation, Software and Firmware to ensure reliable operation of the system (down-
loadable from www.wieland-electric.com).
The UPS 20-960 is a microprocessor controlled unit that can perform two functions:
UPS rated 960 W / 20 A usable in any system rated 12 ... 48 V DC
DC-DC converter (non-isolated) rated 960 W / 20 A usable in any combination of IN/OUT voltages
12 ... 48 V DC
For the UPS function, it may use a battery of 12 V, independently of the operating load voltage. For any
supply voltages (12 ... 48 V DC) it may use also multiple battery configuration (10 ... 58 V DC). The UPS
module monitors the voltage coming from a DC power supply and in case of power failure a backup
battery is supplying the energy to the load. In normal condition the battery is kept charged by an inte-
grated battery charger supporting various battery chemistries.
As a DC-DC converter (no battery present) the input must be connected to the battery connector. The
input voltage is converted to any output voltage as per the set-up.

3.1 Overview of the UPS module's front

1
2
3
4
5

Figure 1 Front panel view

8
9
10
11

Figure 2 Terminal block 1

Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018
1. Alarm LED indicator: ON when the unit is in
backup. Blinks at 1 Hz rate in case of error.
2. Modbus over USB: Used to connect a PC with
user software or custom application for remote
monitoring and controlling. Firmware update is
also possible through USB connection.
6
3. Temperature sensor: Optional temperature sen-
wipos
sor (
UPS 20 Sensor) to measure the battery
temperature for protection and temperature com-
7
pensated charge method.
4. Terminal block 1
5. Terminal block 2
6. Display area: provides information regarding the
device status.
7. Control keys: 4 push buttons are provided to navi-
gate through the menus and to select the various
functions.
8. Relays dry contacts: 2 relays (signal contacts) are
present for remote monitoring. See no. 26 in sec-
tion 6.2 for more details.
9. Modbus over RS485: Used to connect a PC with
user software or custom application for remote
monitoring and controlling. Firmware update is
also possible through RS485 connection.
10. Inhibit input: A voltage between 5 V DC and
30 V DC applied to this input activates the inhibit
function. See section 5.4 for more details.
3 | Product description
N OTE
8

Advertisement

Table of Contents
loading

Related Products for Wieland Wipos UPS 20-960

This manual is also suitable for:

81.000.6230.0

Table of Contents