Page 1
UPS 20-960 Uninterruptable Power Supply USER MANUAL Doc.-No. BA001052 Updated: 11/2018 (Rev. A)
Page 2
COPYRIGHT This document is copyright-protected. The rights derived from this cop- yright are reserved for Wieland Electric GmbH. Reproduction of this doc- ument or parts of this document is only permissible within the limits of the statutory provision of the Copyright Act. Any modification or abridg- ment of the document is prohibited without the express written agree- ment of Wieland Electric GmbH.
"Danger" or "Warning" are strictly used for cases which present a risk to life or limb. Damage to property only falls into these categories if there is also a risk of personal injury that corresponds to these levels. Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
Page 6
Keep the unit away from fire and water Attention! Ensure appropriate installation before start of operation. Do not cover any air ventilation holes. A T T E NT I O N Use the device only as intended. Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
This product contains high quality materials and components which can be recycled. At the end of its life this product MUST NOT be mixed with other commercial waste for disposal. Check the terms and con- ditions of your supplier for disposal information. Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
RS485 connection. 10. Inhibit input: A voltage between 5 V DC and 30 V DC applied to this input activates the inhibit function. See section 5.4 for more details. Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
UPS mode or to the Figure 3 Terminal block 2 power supply in DC-DC mode. Although the unit is protected the correct polarity must be respected Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
PC user software used for: • Connection through Modbus • Remote monitoring and configuration • Firmware upgrade • Same functionalities of the embedded user interface with the ease of the PC benefits Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
Monit oring and cont rol Bat t ery healt h Modbus/RTU m onit or RS485 uCont roller 2xRelays Inhibit Figure 4 Simplified block diagram for UPS 20-960 Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
Coulomb counter: Estimates the remaining battery capacity and consequently the available backup time. • Deep discharge protection: It protects against the deep discharge of the battery which can lead to its irreversible damage. Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
Rate of Temperature Increase (ΔT/dt): The battery temperature is rising at a rate equal or supe- rior to 1 °C/min. To avoid unattended end of charge do not place the system on an ambient with rapid changes of temperature (for example exposed to direct sunlight). Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
For Supercapacitor after the constant current phase the algorithm goes directly to maintenance keeping the voltage at battery charge voltage. Constant current Maintenance Voltage Charge voltage Charge current Current Time Figure 9 Figure 7: Supercapacitors charging algorithm Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
OFF and then ON again. User must enable in the PC BIOS the automatic start in case of supply The diagram below shows the UPS module's behavior when Shutdown and Automatic restart is enabled. Figure 10 Shutdown and restart chart Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
• Remotely through inhibit input: When enabled on the user setting (see no. 32 in section 6.2), the device can be cold stared toggling the inhibit status from true to false. Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
Input and output are protected against over current with user settable limits. See section 5.3 for more details. When used as a DC-DC converter, the input supply must be connected to the battery connector as shown on Figure 11. Figure 11 DC-DC connection example Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
An opto-isolated input allows the inhibition of the backup function in UPS mode or switching off the output on DC-DC mode. The polarity of the input can be defined using the "Inhibit polarity" field. See no. 28 in section 6.2 for more details. Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
Table 4 User interface layout Symbol Name Function MENU key Menu selection / navigation UP/DOWN keys navigation and selection in menu and to values OK key confirm selection Table 5 User interface keys Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
The baud rate for Modbus over RS485 serial port. Default Value Values (Modbus value) 38400 9600 (1), 19200 (2), 38400 (3), 57600 (4), 115200 (5) Unit LCD name Modbus address Modbus baudrate 0x1001 Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
Page 25
Default Value Range Resolution 10 V 10 … 58 V 0.1 V Unit LCD name Modbus address Volts Bat. Float U 0x1013 Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
Page 26
Threshold for the "Battery over temperature" alarm (see no. 4 in section 6.4.2). Default Value Range Resolution 60 °C -40 … 60 °C 1 °C Unit LCD name Modbus address Degree Celsius Bat. max. T 0x1019 Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
Page 27
DC-DC mode: The UPS module corresponds to the regulated output voltage. Default Value Range Resolution 10 V 10 … 58 V 0.1 V Unit LCD name Modbus address Volts Output nominal U 0x1021 Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
Page 28
Back. time max 0x1025 25 Buzzer enable Enable/Disable buzzer sound in case of alarm. Default Value Values (Modbus value) Disabled Disabled (0), Enabled (1) Unit LCD name Modbus address Buzzer enable 0x1026 Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
Page 29
LCD name Modbus address DC/DC out mode 0x102A 30 Output enable Enable/Disable output. Default Value Values (Modbus value) Enabled Disabled (0), Enabled (1) Unit LCD name Modbus address Output enable 0x102B Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
Page 30
0x1031 36 PC shutdown delay See section 5.1.5 for more details. Default Value Range Resolution 3600 s 1 … 3600 s Unit LCD name Modbus address Seconds PC shutdown delay 0x1032 Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
Page 31
42 Blink output on backup Ton See section 5.1.7 for more details. Default Value Range Resolution 10 s 10 … 600 s Unit LCD name Modbus address Seconds Blink out Ton 0x1041 Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
Page 32
48 Battery charge cycles The value increments automatically at the end of a battery charge cycle. Default Value Range Resolution 0 … 65535 Unit LCD name Modbus address Cycles Bat. charge cycles 0x1104 Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
Modbus address Hours Operating time 0x2020 Battery operating time Hours elapsed since the "Battery installation date" (see no. 41 in section 6.2). Unit LCD name Modbus address Hours Bat. operating time 0x2022 Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
Inactive (0), Active (1) Not used USB powered The UPS module is powered by USB only. LCD name Modbus address USB powered 0x4020 Value 1 Value 2 Inactive (0), Active (1) Not used Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
Page 35
Inactive (0), Active (1) Not used 10 Output disabled Active if the output is disabled in settings. LCD name Modbus address Output disabled 0x4026 Value 1 Value 2 Inactive (0), Active (1) Not used Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
LCD name Modbus address Bat. over temperature 0x4013 Value 1 Value 2 Status 0 → 1: Offending threshold Inactive (0), Active (1) Status 1 → 0: Max. measured value Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
Page 37
(see no. 10 in section 6.2). LCD name Modbus address Bat. deep discharge 0x4019 Value 1 Value 2 Status 0 → 1: Offending threshold Inactive (0), Active (1) Status 1 → 0: Min. measured value Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
Page 38
Active when the measured output current reaches the threshold specified in "Max. output current" field (see no. 22 in section 6.2). LCD name Modbus address Output overload 0x4035 Value 1 Value 2 Inactive (0), Active (1) Not used Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
Page 39
Active when the internal temperature is too high. To prevent damage the device switches OFF. LCD name Modbus address Error over temperature 0x403B Value 1 Value 2 Inactive (0), Active (1) Not used Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...
3 - Shutdown command 4 - Reset command 5 - Inhibit signal 6.5 Wizard (system configuration) The wizard assists the user during the UPS module configuration. It should be run once at commissioning. Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018...