Mitsubishi Electric MUZ-FE09NA Service Manual page 23

Hide thumbs Also See for MUZ-FE09NA:
Table of Contents

Advertisement

10-3. TROUBLESHOOTING CHECK TABLE
No.
Symptom
LED indication
Outdoor unit
1-time blink every
does not oper-
2.5 seconds
1
ate.
2
3
6-time blink
4
2.5 seconds OFF
11-time blink
5
2.5 seconds OFF
14-time blink
6
2.5 seconds OFF
'Outdoor unit
2-time blink
stops and
2.5 seconds OFF
7
restarts 3 min-
utes later' is
repeated.
3-time blink
2.5 seconds OFF
8
4-time blink
2.5 seconds OFF
9
5-time blink
10
2.5 seconds OFF
8-time blink
2.5 seconds OFF
11
10-time blink
2.5 seconds OFF
12
12-time blink
13
2.5 seconds OFF
13-time blink
14
2.5 seconds OFF
Outdoor unit
1-time blink
15
operates.
2.5 seconds OFF
3-time blink
2.5 seconds OFF
16
4-time blink
2.5 seconds OFF
17
NOTE: 1. The location of LED is illustrated at the right figure. Refer to 10-6.1.
2. LED is lit during normal operation.
The blinking frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the blinking frequency is "2".
ON
2.5-second OFF
OFF
OBH543G
Abnormal point/
Condition
Outdoor power sys-
Overcurrent cut-out operates 3 consecutive times within 1
tem
minute after the compressor gets started, or failure of restart of
compressor has repeated 24 times.
Outdoor thermistors Discharge temperature thermistor, fin temperature thermistor,
defrost thermistor, outdoor heat exchanger temperature ther-
mistor, P.C. board temperature thermistor or ambient tempera-
ture thermistor shorts or opens during compressor running.
Outdoor control sys-
Nonvolatile memory data cannot be read properly.
tem
[POWER lamp (MSZ-FE09/12NA)/the upper lamp of OPERA-
TION INDICATOR lamp (MSZ-FE18NA) of the indoor unit
lights up or blinks 7 times.]
Serial signal
The communication fails between the indoor and outdoor unit
for 3 minutes.
Stop valve/
Closed valve is detected by compressor current.
Closed valve
Outdoor unit
Outdoor unit is defective.
(Other abnormality)
Overcurrent protec-
Large current flows into intelligent power module.
tion
MUZ-FE09/12NA, MUZ-FE12NA1, MUZ-FE09/12NAH
*When overcurrent protection occurs within 10 seconds after
compressor starts, compressor restarts after 15 seconds.
Discharge tempera-
Temperature of discharge temperature thermistor exceeds 241°F
ture overheat protec-
(116°C), compressor stops. Compressor can restart if discharge
tion
temperature thermistor reads 212°F (100°C) or less 3 minutes
later.
Fin temperature /
Temperature of fin temperature thermistor on the heat sink
P.C. board tempera-
exceeds 167 ~ 176°F (75 ~ 80°C) or temperature of P.C. board
ture thermistor over-
temperature thermistor on the inverter P.C. board exceeds 158
heat protection
~ 167°F (70 ~ 75°C).
High pressure pro-
Temperature of indoor coil thermistor exceeds 158°F (70°C) in
tection
HEAT mode. Temperature of outdoor heat exchanger tempera-
ture thermistor exceeds 158°F (70°C) in COOL mode.
Compressor syn-
The waveform of compressor current is distorted.
chronous abnormal-
ity
Outdoor fan motor
Outdoor fan has stopped 3 times in a row within 30 seconds
after outdoor fan start-up.
Each phase current
Each phase current of compressor cannot be detected nor-
of compressor
mally.
DC voltage
DC voltage of inverter cannot be detected normally.
Frequency drop by
Current from power outlet is nearing Max. fuse size.
current protection
Frequency drop by
Temperature of indoor coil thermistor exceeds 131°F (55°C) in
high pressure pro-
HEAT mode, compressor frequency lowers.
tection
Frequency drop by
Indoor coil thermistor reads 46°F (8°C) or less in COOL mode,
defrosting in COOL
compressor frequency lowers.
mode
Frequency drop by
Temperature of discharge temperature thermistor exceeds 232°F
discharge tempera-
(111°C), compressor frequency lowers.
ture protection
0.5-second ON
2.5-second OFF
Condition
0.5-second ON
23
Remedy
• Reconnect connector of compres-
sor.
• Refer to 10-5.
"How to check in-
verter/compressor".
• Check stop valve.
• Refer to 10-5.
"Check of outdoor
thermistors".
• Replace inverter P.C. board.
• Refer to 10-5.
"How to check
miswiring and serial signal error.
• Check stop valve.
• Refer to 10-2.2. "Flow chart of the
detailed outdoor unit failure mode
recall function".
• Reconnect connector of compres-
sor.
• Refer to 10-5.
"How to check in-
verter/compressor".
• Check stop valve.
• Check refrigerant circuit and refrig-
erant amount.
• Refer to 10-5.
"Check of LEV".
• Check around outdoor unit.
• Check outdoor unit air passage.
• Refer to 10-5.
"Check of outdoor
fan motor".
• Check refrigerant circuit and refrig-
erant amount.
• Check stop valve.
• Reconnect connector of compres-
sor.
• Refer to 10-5.
"How to check in-
verter/compressor".
• Refer to 10-5.
"Check of outdoor
fan motor.
• Refer to 10-5.
"Check of inverter
P.C. board.
• Refer to 10-5.
"How to check in-
verter/compressor".
• Refer to 10-5.
"How to check in-
verter/compressor".
The unit is normal, but check the
following.
• Check if indoor filters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air cir-
culation is short cycled.
• Check refrigerant circuit and refrig-
erant amount.
• Refer to 10-5.
"Check of LEV".
• Refer to 10-5.
"Check of outdoor
thermistors".
Inverter P.C. board (Parts side)
MUZ-FE09/12NA
LED
MUZ-FE12NA1
Blinking →
MUZ-FE09/12NAH
MUZ-FE18NA
LED

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents