7. Connect the ground wire from the power source /
electrical panel to the ground stud of the outlet
box.(Green)
8. Connect the ground wire from the air cleaner to the
ground stud of the outlet box.(Green)
9. Use one wire nut to connect the black color-coded,
lead wire on the remote switch to the black color-
coded wire from the power source/electrical panel.
10. Fold wires into box and mount remote switch on out-
let box. Leave switch in OFF position.
At AIR CLEANER:
11. On the air cleaner remove two screws on wiring com-
partment cover and open
12. Run the five conductor, color coded, 18 gauge wires
from the remote switch through the air cleaner
access opening into the wiring compartment. Strip
ends of these lead wires.
13. Connect three wires from air cleaner to remote switch
lead wires with wire nuts following color code used at
remote switch. (Red, Blue, Violet)
14. Connect the white wire on air cleaner to power
source/electrical panel Neutral wire with a wire nut
following color code used at remote switch. (White)
15. Connect the ground wire from the remote switch to a
ground stud of the wiring compartment cover.(Green)
16. Fold wires into wiring compartment. Replace wiring
compartment cover.
17. Turn on power to air cleaner at power source/electri-
cal panel.
18. Check operation by turning air cleaner at HIGH,
MEDIUM, and LOW. Note that only the remote switch
will operate the air cleaner.
Lid Assembly
The F111 lid is held in place by two separable hinges and
two spring loaded plungers. To install the spring loaded
plungers on the lid follow these steps:
1. Pull the plunger back and twist a quarter turn to
reveal the wrench flat on the body of the spring
loaded plunger (see Fig. 7.)
2. Turn the threaded barrel out of the spring plunger.
3. Insert the threaded barrel through the hole in the lid
and turn the spring loaded plunger onto it.
4. Tighten the assembly with wrenches.
5. Repeat steps 1 through 4 for the second plunger.
Opening/Closing the Lid
To open the lid, pull the spring loaded plungers back to
disengage the plunger. Carefully swing the lid open on the
hinges while supporting the filter and/or adsorbent
modules as required. To close, swing the lid into the closed
position and engage the plungers.
Removing /Replacing the Lid
IMPORTANT
The lid is heavy. Make sure that it is supported
before removing.
F111 (SERIES 3) IN CEILING MEDIA AIR CLEANER
6. To remove the lid, swing it into the open position.
Slide safety catch to off position. Move the lid to the
side to disengage the hinge pins. Reverse the proce-
dure to replace the lid. Make sure safety catch is in
safe position.
Fig. 7. Lid assembly.
OPERATION
The F111 (Series 3) in Ceiling Media Air Cleaner has been
engineered to improve indoor air quality for commercial
and industrial applications. The filters are the most
practical and effective filtering system for removing
atmospheric dust, pollens, bacteria, viruses, mold spores,
smoke, fumes, mists and aerosols. Refer to Fig. 8.
BLOWER
CPZ™
SORBENT
MOTOR
FILTER
MODULE
CEILING LINE
CLEAN AIR
DISCHARGE
AIR IN
Fig. 8. F111 (Series 3) air cleaner operation.
The air cleaner is either operating (power on) or off (power
off). There are no other operational options available. Even
when the area is unoccupied, the air cleaner can be
operated continuously to prevent buildup of airborne
contaminants. Operate the air cleaner only when the area
is occupied when specific activities produce contaminants.
7
WRENCH FLAT
THREADED
BARREL
WRENCH
FLAT
SPRING
LOADED
PLUNGER
AIR VENTS
INTAKE
CEILING LINE
PARTICLE FILTER
CLEAN AIR
DISCHARGE
PREFILTER
AIR IN
M11994
CPZ™
SORBENT
FILTER
MODULE
M12651A
68-0198—05