3. Installation

3.8 Multiple Transformer Connections

WARNING: The transformer output neutral is not bonded to chassis ground. Please provide a means
to connect the transformer chassis ground to the transformer output neutral.
Note: The transformer chassis ground must be connected to earth ground.
IMPORTANT: You may view and/or download this manual from the tripplite.com website to view the
cable connections in colors.
3.8.1 Connections for S3MT-60K480V/S3MT-60K600V to S3M50K or S3M60K UPS
Transfomer input is Delta 3-Wire (3Ph + Ground) And transformer output is Wye 4-Wire (3Ph + N + Ground).
Figure 3-8: UPS (Rear View)
3.8.2 Connections for S3MT-100K480V/S3MT-100K600V to S3M80K or S3M100K UPS
Transfomer input is Delta 3-Wire (3Ph + Ground) And transformer output is Wye 4-Wire (3Ph + N + Ground).
Figure 3-9: UPS (Rear View)
Transformer Cabinet (Front View)
Transformer Cabinet (Front View)
15