Power Cables - Tripp Lite S3MT-Series Owner's Manual

3-phase input transformers
Table of Contents

Advertisement

Available languages

Available languages

3. Installation

3.6 Power Cables

The cable design shall comply with the voltages and currents provided in this section, and in accordance with local electrical codes.
WARNING!
UPON STARTUP, ENSURE YOU ARE AWARE OF THE LOCATION AND OPERATION OF THE EXTERNAL
ISOLATORS CONNECTED TO THE UPS INPUT/BYPASS SUPPLY OF THE UTILITY DISTRIBUTION PANEL.
ENSURE THESE SUPPLIES ARE ELECTRICALLY ISOLATED AND POST ANY NECESSARY WARNING SIGNS TO
PREVENT INADVERTENT OPERATION.
Cable Sizes
AC Input
UPS Model
Gauge
50mm
2
S3MT-
Max.
60K480V
50mm
x2
2
35mm
2
S3MT-
Max.
60K600V
50mm
x2
2
70mm
x2
2
S3MT-
Max.
100K480V
120mm
x2
2
50mm
2
S3MT-
Max.
100K600V
70mm
x2
2
Cable Sizes (THHW wiring at 75°C)
AC Output
Torque
Gauge
50mm
2
25N•m
Max.
50mm
x2
2
50mm
2
25N•m
Max.
50mm
x2
2
70mm
x2
2
50N•m
Max.
95mm
x2
2
70mm
x2
2
50N•m
Max.
95mm
x2
2
Neutral
Torque
Gauge
70mm
x2
2
25N•m
Max.
70mm
x2
2
70mm
x2
2
25N•m
Max.
70mm
x2
2
120mm
x2
2
50N•m
Max.
120mm
x2
2
120mm
x2
2
50N•m
Max.
120mm
x2
2
12
Grounding
Torque
Gauge
50mm
2
25N•m
Max.
50mm
x2
2
50mm
2
25N•m
Max.
50mm
x2
2
95mm
2
50N•m
Max.
120mm
2
95mm
2
50N•m
Max.
120mm
2
Lug
Torque
25N•m
M8
25N•m
M8
50N•m
M10
50N•m
M10

Advertisement

Table of Contents
loading

This manual is also suitable for:

S3mt-60k480vS3mt-100k480vS3mt-60k600vS3mt-100k600v

Table of Contents