NK TECHNOLOGIES ATQ Series Instructions

Ac transducers

Advertisement

Quick Links

Specifications
Output
Open collector transistor, opto-
isolated pulse width
5kHz: On -- 90-100 µS, Off: Variable
Pulse Width
10kHz: On -- 45-50 µS, Off: Variable
Current
2mA @ 8 VDC minimum
15mA @ 24 VDC maximum
Voltage
5-27 VDC
Limits
Capped to 125% of range
05K model: 6.25kHz max
10K model: 12.5kHz max
Accuracy
1% FS
Isolation Voltage
5kV (Input to Output, Power to
Output)
Response Time
100 mS (to 90% of step change)
Input Freq. Range
10-400 Hz
Input Current Ranges Field Selectable from 0-200 AC Amps
(See Ordering Information)
Power Supply
24 VAC/VDC nominal
(19.2 - 26.4 VAC/VDC range)
Power Consumption
<1 VA
Case
UL 94V-0 Flammability rated
thermoplastic
Environmental
-20 to 50 Deg. C, 0-95% RH, non-
condensing
Input Maximums
MAXIMUM INPUT AMPS
MODEL RANGE
6 SEC.
ATQ0
0-2A
125
0-5A
125
ATQ1
0-10 A
125
0-20 A
150
0-50 A
215
ATQ2
0-100 A
300
0-150 A
450
0-200 A
500
Model Number Key
ATQ 1 - 10K - 24U - SP
OUTPUT:
05K 0-5 kHz
10K 0-10 kHz
RANGE
0 - 0-2 or 5 Amps
1 - 0-10, 20 or 50 Amps
2 - 0-100, 150 or 200 Amps
SENSOR TYPE:
ATQ - AC current transducers, average responding
Know Your Power
Other NK Technologies Products Include:
AC & DC Current Operated Switches & Transducers
Ground Fault Sensors
1φ & 3φPower Transducers
Current & Potential Transformers (CTs&PTs)
1 SEC.
250
250
250
300
400
3511 Charter Park Drive, San Jose, CA 95136
600
Toll free: 800-959-4014
Fax: 408-871-7515
800
sales@nktechnologies.com, www.nktechnologies.com
1,000
CASE STYLE
SP- Split Core
POWER SUPPLY:
24U- 24VAC/DC
3
Phone: 408-871-7510
INSTRUCTIONS
PATENTED
ATQ SERIES
AC Transducers
Frequency Output, Avg. Responding
Quick "How To" Guide
1. Route monitored wire through aperture, mount using
two screws and mounting feet.
2. Connect 0-5Hz/0-10Hz output to PLC (or other meter
device) using 14-18 AWG copper wires. Ensure
polarity is correct for Sink or Source connection (see
"Output Wiring" section) and programmed PLC
settings match recommended bandwiths.
3. Power supply must be 24VAC/VDC. Connect using 14 -
18 AWG copper wires. Power LED should be on
whenever power is connected to the unit.
4. Choose input range by positioning the Range Jumper.
Facing the 3-pin jumper, position jumper over top two
pins for High range, bottom two pins for Mid range,
and no jumper for Low range.
5. With current flowing through unit, check for proper
operation by confirming frequency output is propor-
tion to input current.
ATQ Instructions, 09/10, Rev3 P/N 29-210-0001

Advertisement

loading

Summary of Contents for NK TECHNOLOGIES ATQ Series

  • Page 1 14-18 AWG copper wires. Ensure polarity is correct for Sink or Source connection (see “Output Wiring” section) and programmed PLC Other NK Technologies Products Include: settings match recommended bandwiths. AC & DC Current Operated Switches & Transducers Input Maximums Ground Fault Sensors 3.
  • Page 2 Digital Inputs (DIs) to SINK or SOURCE connection (diagrams below). accept and process an analog value. ATQ Series provide an “Average Responding” output. Se- lect ATQ Series for constant speed motors or On/Off loads such as lamps or heaters. Installation For All Versions Run wire to be monitored through opening in the sensor.