Warmco HR10 Instruction Manual page 21

Premix unit air heater
Table of Contents

Advertisement

error
L-33, 34,
Internal
35, 36,
error
37, 38
Temperately errors, the will disappear when the cause is taken away
Display
E00, to
Internal
04
error
E-05
Overheat
E-06 to
Internal
13
error
E-14
Flame error
E-15 to
Internal
22
error
E-23, 24
Flue sensor
E-30-31
Flue sensor
E-34
Reset
button
E-36
Overheat
E-38, 39
Heat
exchanger
sensor
E-48, 48
Heat
exchanger
sensor
Case 1: Within 5 sec flame, then flame failure.
The flame is not detected. Check the ignition cable and electrode. (cable resistance 1k
Ohm).
The electrical earth of the heater is poor,
The print board is defective.
Case 2:
There is not enough gas pressure.
The mixture of gas/air is poor, adjust the gas valve
The gas valve does not open, check during ignition for 230V on the valve.
Check whether the ignition electrode sparks, replace cable, electrode
Case 3: Heat exchanger too hot
Check whether the system fan blows enough air.
Check the setting of the gas valve, the heater may me overloaded.
Case 4: Temperature sensor on heat exchanger error.
The sensor has internally 2 sensors. These differ too much. Measure the resistance
from each sensor, the resistance should be 20K at 25° en 25K at 20° . If the measured
values differ too much, replace sensor.
L-25 is heat exchanger sensor, L-26 is flue sensor
Case 5: Too many flame failures while burning
The setting of the gas valve is not ok, adjust the gas valve
The flue outlet is blocked
Case 6: The premix does not run
Premix fan is Blocked or the wiring is bad
Premix fan is defective
Case 7: The pre-mix fan runs, but not the correct speed.
Check if the fan runs smoothly.
Check the wiring.
Case 9: Reset button error
Too many switches on reset button in a short period of time. These error will disappear
after some time, or if the main power is disconnected for a while.
Instructions condensing Air heaters type HR version HR-GB-4001-a
Internal error
Explanation
Internal error
Overheat heat exchanger sensor
Internal error
Flame detection when that should not be
Internal error
Flue sensor not detected
Flue sensor shortened
Too many reset actions in a short time
Overheat heat exchanger sensor
Sensor heat exchanger not detected
Heat exchanger sensor shortened
13
Cause
13
3
13
16
13
9
3
4
4