16-ch counter/frequency board
with 32-ch programmable dio (49 pages)
Summary of Contents for ICP DAS USA A-626
Page 1
The user can use, modify and backup this software The user may not reproduce, transfer or distribute this software, or any copy, in whole or in part. A-626 / A-628 User’s Manual (Ver.1.3, Jun/2009, IMH-005-13) ----- 1...
: Voltage output : 0 ~ 5 V,0 ~ 10 V,±5 V,±10 V or Current loop :4 ~ 20 mA . The A-626/ A628 has 16 channel digital input and digital output . All the D/I/O channel are TTL compatible. and it can connection with DB-16P (16 channel isolation digital input board) or DB-16R(16 Channel Relay output board) daughter board.
90 mA @ -12 V (Max.) 105 mA @ -12 V (Max.) Operating Temperature 0 ~ 60 °C Storage Temperature -20 ~ 70 °C Humidity 5 ~ 85% RH, non-condensing A-626 / A-628 User’s Manual (Ver.1.3, Jun/2009, IMH-005-13) ----- 5...
2.2. Jumper and DIP Switch Setting When you use the A-626 / A-628, You should set the I/O address and voltage range first. You can configure output voltage of each channel and I/O address by jumper and switch.
A8 A7 A6 Default Base Address: 2C0 Hex For Example How to select 2 C 0 (Hex) The detail SW1 base addresses setting. Please refer to A-628 Base Address Table. A-626 / A-628 User’s Manual (Ver.1.3, Jun/2009, IMH-005-13) ----- 11...
278-27F Parallel Port 3B0-3BF MDA/Parallel Port 2B0-2DF 3C0-3CF 2E0-2E7 AT GPIB 3D0-3DF 2E8-2EF Serial Port 3E0-3EF Serial Port 2F8-2EF Serial Port 3F0-3F7 Floppy Disk 300-31F Prototype Card 3F8-3FF Serial Port A-626 / A-628 User’s Manual (Ver.1.3, Jun/2009, IMH-005-13) ----- 12...
+7(495)109-02-08 sales@bbrc.ru www.bbrc.ru 2.5. Jumper Setting 2.5.1. A-626 Jumper Setting The A-626 each D/A channel can be configurable. You can set the voltage range for your applications. The A-626 provides -5 V or -10 V internal reference voltage and unipolar or bipolar voltage output.
ГК Атлант Инжиниринг – официальный представитель в РФ и СНГ +7(495)109-02-08 sales@bbrc.ru www.bbrc.ru 2.6. Pin Assignment A-626 P1: 37-Pin Connector for Voltage Output & Current Loop CH0 V.Out CH4 V.Out CH0 Ext Ref In CH0 I .Out CH4 Ext Ref. In A.
Page 18
D/A External Reference Input Channel n CH n I. Out Current Loop Output Channel n A.GND Analog Ground D.GND Digital Ground PC’s +5 V From PC Power Supply +5 V A-626 / A-628 User’s Manual (Ver.1.3, Jun/2009, IMH-005-13) ----- 18...
Page 19
DO 15 +5 V +12 V The A-626 / A-628 has 16 channel digital output /Input , all of the digital channels are TTL compatible. The DB-16R ( 16 Channel Relay Actuator Board) or DB-24PR (24 Channel Power Relay Actuator Board) and DB-16P (16Channel Isolation Input Board) are designed...
Output Current Max (±5 mA) Convertor Load DATA 12-Bit A.GND The A-626 / A-628 D/A Voltage Output Maximum Current :± 5 mA 2.7.2. Current Loop Current Loop 4 ~ 20 mA A-626 I. Out LOAD D/A 0 ~ 5 V...
Base + 2 Base + 3 Base + 4 Base + 5 Base + 6 Base + 7 Base + 8 Base + 9 Base + A Base + B A-626 / A-628 User’s Manual (Ver.1.3, Jun/2009, IMH-005-13) ----- 21...
Base + 0x6 Base + 0x7 Base + 0x8 Base + 0x9 Base + 0xA Base + 0xB Base + 0xC Base + 0xD Base + 0xE Base + 0xF A-626 / A-628 User’s Manual (Ver.1.3, Jun/2009, IMH-005-13) ----- 22...
‘Unipolar 0 ~ 5 V D/A Channel 0 will output 2.5 V High Byte Data Low Byte Data D7 D6 D5 D4 D3 D2 D1 D0 D7 D6 D5 D4 D3 D2 D1 D0 0x000 0x800 0xFFF 12 Bit Data A-626 / A-628 User’s Manual (Ver.1.3, Jun/2009, IMH-005-13) ----- 23...
Page 24
+10 V 4 mA (4 ~ 20 mA) 12 mA 20 mA 0 (0x000) 2048 (0x800) 4095 (0xFFF) 0000 0000 0000 1000 0000 0000 1111 1111 1111 12 bit Data Format A-626 / A-628 User’s Manual (Ver.1.3, Jun/2009, IMH-005-13) ----- 24...
Page 25
Low Byte Data OUT ( BasAddress + 0 , HighByte) ‘ Write high byte data first OUT ( BasAddress + 1 , LowByte) ‘ Then low byte data to D/A channel 0 A-626 / A-628 User’s Manual (Ver.1.3, Jun/2009, IMH-005-13) ----- 25...
‘ Write Data to Channel 8 ~ 15 of Digital Output DIL = INP(Bas + &HC) ‘ Read Channel 0 ~ 7 of Digital Input DIL = INP(Bas + &HD) ‘ Read Channel 8 ~ 15 of Digital Input A-626 / A-628 User’s Manual (Ver.1.3, Jun/2009, IMH-005-13) ----- 26...
ГК Атлант Инжиниринг – официальный представитель в РФ и СНГ +7(495)109-02-08 sales@bbrc.ru www.bbrc.ru 4. Calibration The each channel of A-626 /A-628 has three VR can be adjust to current value. A-626 VR’s Table D/A Channel Unipolar Full Scale Bipolar Off-set...
Page 28
3. Write 0x000 (Hex) to D/A Channel 0 4. Trim VR1-3 until the DAM reading 4.0000 mA 5. Write 0xFFF (Hex) to D/A Channel 0 6. Trim VR1-2 until the DAM reading 20 mA A-626 / A-628 User’s Manual (Ver.1.3, Jun/2009, IMH-005-13) ----- 28...
A-626/ A-628 Digital Input Opto-Isolated A-626 / A-628 20-Pin cable DB-16P AC or DC Signal 0 V ~ 24 V A-626 / A-628 User’s Manual (Ver.1.3, Jun/2009, IMH-005-13) ----- 29...
Normally Closed Com. 20-Pin cable DB-16R A-626 / A-628 Note: Channel : 16 Form C Relay Relay : Switching up to 0.5 A at 110 V 1 A at 24 V A-626 / A-628 User’s Manual (Ver.1.3, Jun/2009, IMH-005-13) ----- 30...
20-Pin connector For 16 Channel digital output, A-82X, A-62X, DIO-64 Channel: 16 Form A Relay, 8 Form C Relay Relay: Switching up to 5 A at 110 V / 5 A at 30 V A-626 / A-628 User’s Manual (Ver.1.3, Jun/2009, IMH-005-13) ----- 31...
I/O signals to 37-pin boards. It includes one 37-pin D-sub connector for direct connection to 37-pin cables with hardware for mounting on a standard DIN rail. A-626 / A-628 37-pin cable DN-37 Wire Wire A-626 / A-628 User’s Manual (Ver.1.3, Jun/2009, IMH-005-13) ----- 33...