Technical Data - JUMO 902428/30 Operating Manual

Temperature probes for heat meters
Table of Contents

Advertisement

3

Technical data

3 Technical data
Temperature range
902428/30, 902428/40
902438/30, 902438/32
Protection type
Temperature difference
Minimum
Maximum
Maximum pressure
902428/30, 902428/40
902438/30, 902438/32
Electrical connection
Maximum measuring current
Response times
Temperature probe, direct mea-
surement
902428/30, 902428/40
Temperature probe, in immersion
sleeve
902438/30, 902438/32
Measurement stability
Minimum immersion depth
Nominal value
Tolerance
6
0 to 180 °C
0 to 180 °C
The maximum operating temperature of the immersion sleeves must be ob-
served.
IP65 (as delivered condition)
In heat applications, it must be ensured that the dew point
is not reached or undershot.
3 K
180 K
PS25 for a water flow velocity of 2 m/s
PS25 for a water flow velocity of 2 m/s
Two-wire, four-wire
The maximum measuring current is calculated using the maximum admissible
power loss of 5 mW.
Depending on the nominal values, this results in the following effective current
values:
Pt100: 1783 µA
Pt500: 797 µA
Pt1000: 564 µA
t
≤ 6.0 s
0.5
t
≤ 12.0 s
0.5
10 years (see also maintenance)
30 mm
Pt100, Pt500, Pt1000 (see identification marking for temperature probes)
Class B according to DIN EN 60751; restricted tolerances optional
When using two-wire technology, the display will be systematically higher due
to the line resistance (see maximum connection length according to
DIN EN 1434).